JOVYTEC PE / PME
100000004673
- 20 -
11 Technical data
11.1 Technical data UPS
Rated power
1000 VA
1500 VA
2000 VA
3000 VA
Output
Rated power (cos φ = 0,9)
1000 VA
1500 VA
2000 VA
3000 VA
Active power at output (cos φ = 1)
900 W
1350 W
1800 W
2700 W
Active power at output (cos φ = 1) with external battery
810 W
1215 W
1620 W
2430 W
Rated output voltage
Adjustable (version 208 V to 240 V)
208/220/
230
/240 VAC *)
Rated output voltage
Adjustable (version 100V to 120V)
100/110/115/
120
VAC *)
Rated output frequency (automatic)
50/60 Hz
Synchronising rate
1 Hz/s
THDU (adherent to IEC EN 62040-3)
- linear load
- non-linear load
< 2.5%
< 5%
Output voltage regulation (static)
+/-2%
Output voltage regulation (dynamic)
(load step 20% < - >100%; linear load)
+/-9%
Overload (online mode)
30 seconds @ 106 - 120%
10 seconds @ 121 - 150%
Overload (battery mode)
10 seconds @ 106 - 115%
3 seconds @ 115 - 150%
Efficiency (AC-AC)
approx. 89%
Rectifier input
Input voltage (version 208 V to 240 V)
230 V -20% / +13%
Input voltage (version 100 V to 120 V)
120 V -20% / +13%
Input frequency (automatic detection)
45 Hz - 65 Hz
Synchronisation range
(based on nominal frequency 50 Hz or 60 Hz)
+/-2% /
+/-5%
/ +/-7% *)
Max. input current (U
nominal
= 230 V)
4.4 A
7.0 A
9.4 A
14.1 A
Max. input current with add. battery charger (Unominal = 230 V)
6.3 A
8.8 A
10 A **)
15 A **)
Max. input current (U
nominal
= 120 V)
---
---
16 A
24 A
Max. input current with add. battery charger (Unominal = 120 V)
---
---
17 A **)
26 A **)
Input power factor (at 100% load)
0.97
Bypass input
Input voltage range (adjustable)
184 - 265 VAC
Battery
Number of battery cells (JOVYTEC PE series)
18
24
36
48
Number of battery blocks (JOVYTEC PE series)
3
4
6
8
Number of battery cells (JOVYTEC PME series)
18
24
36
36
Number of battery blocks (JOVYTEC PME series)
3
4
6
6
Number of battery cells (JOVYTEC PME series, short version)
---
---
36
48
Number of battery blocks (JOVYTEC PME series, short version)
---
---
6
8
Battery charge voltage (per cell)
2.27 V
Battery final discharge voltage (per cell) @load > 30%
1.67 V
Battery final discharge voltage (per cell) @load < 30%
1.80 V
Battery charge characteristic
IU (DIN 41772)
Additional data
EMC class (EN 62040-2)
C1
C1
C2
C2
Classification (EN 62040-3)
VFI SS 111
Noise level
< 45 dB
< 45 dB
< 50 dB
< 50 dB
IP code (DIN EN 60529)
IP 20
Protection class (DIN EN 61140)
I
Cooling
Convection cooling
Finish
RAL 9005
Requirements at the point of installation
Installation elevation
as per EN 62040-3
UPS ambient operating temperature
0 to +40°C
Recommended ambient temperature
+15°C to +25°C
UPS storage temperature (without battery)
-15 to +50°C
Battery ambient/storage temperature
(recommended battery ambient temperature,
see also battery instructions)
0 to +25°C
+20°C
Relative humidity (w/o condensation)
< 95%
Ambient conditions for storage acc. to EN 60721-3-1
1Z1 1B1 1C1 1S1 1M1
Ambient conditions for operation acc. to EN 60721-3-3
3Z1 3B1 3C1 3S1 3M1
Minimum space between rear and wall
100 mm
Minimum space at sides
50 mm
*) Default settings
underlined