JOVYTEC PE / PME 

100000004673 

 - 8 -

 

 

3.2.5 

Audible alarms 

Battery discharging:  

 

 

One short tone sounds every 5 seconds 

When battery close to depletion:    

Two short tones sounds every 5 seconds 

Fault: 

 

 

 

 

Continuous tone 

During battery test: 

 

 

No tone 

 

4  Transport and storage 

Only transport the equipment in its original packaging. Always use the appropriate transport gear. 
Do not remove the original packaging until the equipment has reached its final operating destination. 
Protect against falling when storing! 
Store the equipment in a dry place; see also the technical data. 
 

4.1 

Storing the battery 

If the UPS includes a battery or there is a separate battery unit, observe the following: 
Recharging is required if the battery is stored as follows. 
At approx. 20°C, every 6 months 
At approx. 30°C, every 3 months 
At approx. 35°C, every 2 months 
More information can be found in the battery manufacturer's operating instructions. 
 

4.2 

Unpacking and setup 

 
Keep packaging for return transports. Store it in a dry place. Set up the equipment, making sure that it cannot fall 
over. Alternatively, slide it carefully into a slot designed for UPS systems.  
Note that you must insert it into a slot as far as it will go. 
Refer to the technical data for conditions concerning the setup location.  
 

5  Installation 

This model of UPS either comes with a battery integrated into the housing or with an external battery case. 
Use the cables included in delivery to connect it. 
 
 

CAUTION: 

UPSs from this model series are designed for different  DC-voltages (battery voltages). Always 
check that the battery voltage matches the specifications before connecting an external battery 
to the UPS. There is otherwise a risk of destroying individual assemblies and/or the battery. The 
battery sockets and connectors have been mechanically coded to aid you in avoiding incorrect 
connection. 

 
 

CAUTION: 

Do  not  connect  an  external  battery  until  the  UPS  is  being  fed  an  input  voltage.  There  is 
otherwise a risk of overloading the battery connection. 

 

 

NOTE: 

PME-1000VA has its air outlet on its front side. 
All other models have their air outlet on their rear. 
 

 
Connect the UPS to the supply grid. 
Make sure that the UPS is receiving input voltage. 
If required: Connect an external battery to the UPS. 
Connect consumers to the output sockets. 
 
 

NOTE: 

Refer  to  the  list  of  electrical  connections  for  the  connection  assignments;  see  the  section  on 
technical data for the corresponding technical specifications. 
 

 

 

i

i

Summary of Contents for JOVYTEC PE 1000 VA

Page 1: ...100000004673 W rtsil JOVYATLAS GmbH Fennenweg 4 26844 Jemgum Germany www jovyatlas de Tel 49 0 4958 9394 0 Fax 49 0 4958 9394 10 Operating Manual JOVYTEC PE PME 1000 1500 2000 3000 VA...

Page 2: ...of delivery for products of the electronics industry as well as our general sales conditions We reserve the right to make changes to these instructions in particular as regards the technical data ope...

Page 3: ...E short version only 10 5 1 6 2000VA JOVYTEC PME short version 100V 120V only 11 5 1 7 3000VA JOVYTEC PME short version only 11 5 1 8 3000VA JOVYTEC PME short version 100V 120V only 11 5 1 9 RS 232 in...

Page 4: ...JOVYTEC PE PME 100000004673 4...

Page 5: ...batteries which include AGM and gel batteries are often termed maintenance free batteries The maintenance free feature only relates to the fact that distilled water cannot be topped up and the acid l...

Page 6: ...faces RS 232 USB serial interfaces for reading UPS data standard SNMP adapter for remote monitoring data exchange via a LAN connection option Relay card with alarm messages for industrial remote monit...

Page 7: ...voltage beyond 10 or 15 if configured accordingly of nominal voltage Input frequency beyond 3 Hz threshold You can activate this operating mode on the control panel 3 2 2 Free run mode Free run mode a...

Page 8: ...tems Note that you must insert it into a slot as far as it will go Refer to the technical data for conditions concerning the setup location 5 Installation This model of UPS either comes with a battery...

Page 9: ...USB OPTIONAL USB socket optional INTERFACE OPTIONAL Interface slot for relay card SNMP adapter etc optional EPO Input for UPS electronic power off RS 232 Data signal NETWORK TRANSIENT PROT Ethernet f...

Page 10: ...JOVYTEC PE PME 100000004673 10 5 1 3 1000VA 1500VA JOVYTEC PME 5 1 4 2000VA 3000VA JOVYTEC PME 5 1 5 2000VA JOVYTEC PME short version only...

Page 11: ...JOVYTEC PE PME 100000004673 11 5 1 6 2000VA JOVYTEC PME short version 100V 120V only 5 1 7 3000VA JOVYTEC PME short version only 5 1 8 3000VA JOVYTEC PME short version 100V 120V only...

Page 12: ...ose of a relay card The 3 possible signals are listed in the table below PIN 6 to 9 Type SUB D9 socket Pin no Signal name Signal direction in relation to UPS Function 2 TxD Output Transmit data 3 RxD...

Page 13: ...it when UPS in bypass mode FAULT LED red Lit if there is an internal fault 6 1 2 Buttons Description of buttons on control panel Buttons Description ON OFF On off button To switch on the UPS press and...

Page 14: ...lay reverts to showing the UPS status after a few seconds Display Description O P VOLT xxx xV Output voltage V O P FREQ xx x HZ Output frequency Hz I P VOLT xxx xV Input voltage V I P FREQ xx x HZ Inp...

Page 15: ...ut frequency Free Run Set UPS sets and maintains frequency at nominal value itself ON OFF Bypass on in autonomous mode only shown if free run mode is active Bypass disable When activated the UPS can s...

Page 16: ...ve power at output cos 1 for external battery in the technical data Backup times may be extended by using external battery units in addition to the integrated battery units Connection is established b...

Page 17: ...every 6 months at least 8 1 2 Function test The UPS should be tested for correct operation every six months You may use a test load to do so This will allow a more precise assessment of the UPS s cond...

Page 18: ...of backup Charger Failure Continuous tone Battery charger failure Request service Over Temperature Continuous tone Ambient temperature too high Check the UPS s cooling air flows for blockages reduce a...

Page 19: ...take back UPS units and batteries from the operator free of charge and recycle them accordingly Do not dispose of the equipment with regular household waste 10 Other technical documents We supply the...

Page 20: ...6 A Input power factor at 100 load 0 97 Bypass input Input voltage range adjustable 184 265 VAC Battery Number of battery cells JOVYTEC PE series 18 24 36 48 Number of battery blocks JOVYTEC PE series...

Page 21: ...m 425 mm 84 mm Weight w o integrated battery w o additional charger 10 0 kg 11 6 kg 17 2 kg 18 2 kg Weight w o integrated battery with additional charger 10 7 kg 12 3 kg 18 0 kg 19 0 kg Weight with in...

Page 22: ...short version only Depth Height 428 mm 425 mm 84 mm 428 mm 425 mm 84 mm Additional data Finish RAL 9005 Weight w o integrated battery 8 4 kg 12 2 kg 18 3 kg 18 3 kg Weight with integrated battery 24 3...

Reviews: