BAX 3330 E 

 

     UPS-Division                                                                                                                                Issued 15. August 2006

 

 
 
 
 
 
 
 
 
 
 
 

 

Operating manual 

 

UPS - System 

 

POWERMASTER

POWERMASTER

POWERMASTER

POWERMASTER

 

M

M

M

M

 MIL 

1000VA – 7Min. 

 

 

 

 

 

 

 

 

 

JOVYATLAS 

 

 

 

 

 

 

 

 

Elektrische Umformtechnik GmbH 

 

 

 

 

 

 

 

 

Groninger Straße 29-37 

 

 

 

 

 

 

 

 

D-26789 Leer/Ostfriesland 

 

 

 

 

 

 

 

 

P.O. Box 1580 / D-26765 Leer 

 

 

 

 

 

 

 

 

Tel.:  ++ 491 6002 - 0 

 

 

 

 

 

 

 

 

Fax.: ++ 491 6002 - 10 

 

 

 

 

 

 

 

 

E-Mail: GL@JOVYATLAS.DE 

 

 

 

 

 

 

 

 

Internet: WWW.JOVYATLAS.DE

 

 

 

 

 

 

 

_______________________               

JOVYATLAS 

Summary of Contents for Powermaster ? 1000

Page 1: ...OWERMASTER POWERMASTER POWERMASTER M M M M MIL 1000VA 7Min JOVYATLAS Elektrische Umformtechnik GmbH Groninger Straße 29 37 D 26789 Leer Ostfriesland P O Box 1580 D 26765 Leer Tel 491 6002 0 Fax 491 6002 10 E Mail GL JOVYATLAS DE Internet WWW JOVYATLAS DE _______________________ JOVYATLAS ...

Page 2: ...oughly before installation Pay attention to each relevant information especially the specific comments on the separate chapters Careful reading will avoid malfunctions of the device later on If there is any problem please contact our service division ...

Page 3: ... UPS system 8 6 2 Commissioning of the UPS system 8 6 3 Shut down of the UPS system 9 7 Operating and display elements for 115V Series 10 7 1 Display of the loading of the UPS system for 115V Series 11 7 2 Display of the charge state of the batteries for 115V Series 11 7 3 Handling of the panel for 115V Series 12 8 Alarm messages for 115V Series 13 8 1 Displayed alarm messages for 115V Series 13 8...

Page 4: ...ation temperature would decrease the autonomy time Don t connect devices with connection cables exceeding the length of 10 meters This measure serves for the observance of the EMV norm It s not allowed to carry out structural changes on the UPS Improper operation causes the extinction of warranty Relevant information To prevent self discharging of the batteries you have to connect the UPS to mains...

Page 5: ... battery is permanently charged in a careful way by the charging rectifier in trickle charge mode 3 Description of the functions Normal operation In normal operation the battery and the inverter are fed by the rectifier online operation The conversion of the AC voltage into DC voltage and back into AC voltage ensures a sinusoidal output voltage with a low distortion The DC voltage is also necessar...

Page 6: ...wave Output power factor cos φ 0 7 Frequency 50Hz 60Hz 0 5 Distorsion 3 at linear Load Overload capability 105 for 10s 130 for 300ms Crest Factor 3 1 Operation mode Online Signalisation Data processing interface Radio interferance degree Acc EN 50091 2 1994 Klasse B According to the rules of CE EN IEC VDE Loudness 45 dBA Temperature 0 C 55 C If temperature is exceeding 55 C the ups will switch to ...

Page 7: ...OWERMASTER M series 115V 483 131 technical modifications are possible 5 2 Back view POWERMASTER M series 115V Attention in this case the main input plug and the load output plug are modified in that way that there are special input socket and output socket are used on the rear side of the ups ...

Page 8: ... input mains BYPASS direct bypass onto the input mains LOAD load of the UPS in BATTERY battery state in After approx 5 seconds further on the announcement INV inverter appears The signal BYPASS goes out The consumer plug backsides the UPS is fed by the inverter now For controlling its correct functioning disconnect the UPS from the mains but don t switch it off Now the message LINE extinguishes an...

Page 9: ...the UPS switches over onto bypass operation BYPASS because of the high initial currents of the connected loads That s a normal occurrng the UPS gets back to inverter operation INV after a few seconds If you recognize deviations please contact us see also page 2 6 3 Shut down of the UPS system To switch off the UPS please press the off button in front of the ups the ups will be initialized again an...

Page 10: ...PS system 8 888 8 Digital display of the data 9 I P Display in connection with the input data 10 O P Display in connection with the output data 11 Vac Display in connection with the input output voltage 12 Hz Display in connection with the input output frequency 13 C Temperature of the UPS system 14 ON Switch on of the UPS system 15 OFF Switch off the UPS system 16 SELECT Selector switch of the fu...

Page 11: ...3 loading of the UPS amounts to 41 60 4 loading of the UPS amounts to 61 80 5 loading of the UPS amounts to 81 100 7 2 Display of the charge state of the batteries for 115V Series At the display of the UPS the actual charge state of the system is shown through a segment display 1 loading of the battery amounts to 0 20 2 loading of the battery amounts to 21 40 3 loading of the battery amounts to 41...

Page 12: ...5Hz 4 output frequency normal 50Hz or 60Hz 3Hz 5 Temperature The temperature is dependent on the loading and on the surrounding temperature of the UPS system Critical range 55 C In this case the ups will switch to bypass the load isn t buffered by the ups until the temperatue will be less then 55 C Vac Hz C R S T I P O P LOAD BATT LINE BY PASS INV BACKUP FAULT INV 0 20 40 60 80 100 0 20 40 60 80 1...

Page 13: ...C on the part of the d c voltage The alarm E05 will be shown at the display and the connected load is supplied through the internal bypass further on E06 Misvoltage of the battery voltage higher than 280VDC The alarm E06 will be shown at the display and the connected load is supplied through the internal bypass further on E07 Battery voltage is too high or too low The alarm E07 will be shown at th...

Page 14: ...pletely Switch off the complete load at the consumer distribution pole of the UPS Switch off the UPS systems POWERMASTER M 1000 through removing the input mains of the device Than you have to press down the push button OFF in front of the display for 2 seconds After a delay of 5 seconds the UPS system will switch off completely In case of no success please contact our service department 8 3 Acoust...

Page 15: ...Logic Technical deviations are possible 10 Maintenance In case of longer standstill of the UPS 4 weeks the battery has to be charged monthly For this charging you only have to connect the UPS to the mains for a charging time of at least 8 hours However we recommend a charging time for about 24 hours The battery in its standard version is maintenance free Please note the hints of the battery manufa...