Wärtsilä JOVYTEC PNT 1000VA 

 3000VA   BAX 3313_en

- 24 -

 

7.5 

Automatic/Manual battery test 

Automatic battery test 

In the interval of one month the UPS unit performs an automatic battery test. The UPS will return to normal 
operating mode after the battery test has been performed successfully. 

It is not necessary to operate any 

switches to do this!! 

If the battery is faulty, the message 

Battery fault 

will be shown in the display and a permanent tone will sound. 

Please replace the battery in this case. 

Manual battery test

 

The UPS unit is capable of conducting a self-test. Pressing the key 

FUNC 

causes the unit to run with its 

configurations menu. Manoeuvre to the point: 

Manual Battery Test. 

Now press the button 

ENTER

. The 

message 

TEST? 

appears in the display.  If you wish to perform a battery test then confirm by pressing the  

key 

ENTER

. The battery test will now be performed by the UPS unit by itself. The UPS unit will then again run 

by itself in its normal operating mode after the battery test has been performed successfully. 

It is not 

necessary to operate any switches to do this!! 

If the battery is faulty, the message 

E07 

will be shown in the display and a permanent tone will sound. 

Please replace the battery. 

7.6 

OFFLINE mode 

The UPS unit can be operated using special settings via the display or with the software supplied in 
offline mode. This operating mode has the advantage of only using a small amount of energy. 
The formalism for setting to OFFLINE mode is as follows: 
-  The key 

FUNC

 must be pressed for 2 seconds to enter configuration mode. 

   The first configuration parameter appears in the display. 
-  The key 

FUNC

 can be used to manoeuvre through the parameters. 

-  Select the parameter point to be altered using the key 

ENTER

, in this case: HE mode 

-  The key 

FUNC

 is then used to manoeuvre through the options for the selected parameter (ON/OFF). 

-  You have the option to select between 10% and 15%, which are the thresholds to be monitored, and if the 
voltage does not meet this criterion then the UPS switches to battery operation.
-  The selected option is confirmed using the key 

ENTER

 and saved by pressing the key again. 

-  Ensure that the settings were adopted in that the display shows: High Efficiency. 
-  The UPS unit will start again automatically after restoration of the mains power and starts in the preset mode 
   after a long period of power loss where the end of the autonomy period was reached and the UPS shut down 
   once the final discharge voltage was reached. 

7.7 

Free running mode 

The text below explains the free running mode. The preset input frequency window of the UPS has a 
range of 45Hz - 65Hz and is referred to in the following as the input frequency range. 
The narrow input frequency range has a frequency range of 49Hz - 51Hz. This range can be set via the display 
and operates in the following ranges: 

I/P input frequency low = 50 x (1-0.02) = 49Hz                           I/P input frequency high = 50 x (1+0.02) = 51Hz 

7.7.1 

Free running ON 

If  the  input  frequency  is  49.3Hz,  this  value  is  within  the  narrow  input  frequency  range.  This  means  that  the 
output frequency is also 49.3Hz (synchronised) and the UPS unit runs in line mode. If the input frequency then 
drops below 49Hz, for example 48Hz, the input frequency is outside the narrow input frequency range but still 
within the broader input frequency window. The output frequency will therefore be 50Hz and the UPS unit will 
remain in line mode. If the input frequency were 43Hz then it would be outside both the narrow and the broader 
input frequency window. The UPS unit switches to battery operation and supplies the load via the inverter with 
50Hz. 

Summary of Contents for Wartsila JOVYTEC PNT 1000 VA

Page 1: ...Operating Manual Uninterruptible Power Supply W rtsil JOVYTEC PNT 1000VA 3000VA BAX 3313_en...

Page 2: ...008 A Heller DNV Certificate added 7 29 08 2008 Th Harms 08 308 Relay card removed Not possible at NT Series 8 23 03 2009 A Heller 09 149 Battery Security Data Sheet added 9 26 03 2010 A Heller 10 113...

Page 3: ...the contract but simply serve as a source of information W rtsil JOVYATLAS EUROATLAS GmbH reserves the right to make any necessary changes to the contents and technology described in this operating m...

Page 4: ...0 VA 1500 VA 16 5 3 FRONT VIEW 2000 VA 3000 VA 17 5 4 REAR VIEW 2000 VA 3000 VA 18 6 ELECTRICAL CONNECTION 18 6 2 COMMISSIONING 20 6 3 UPS SHUT DOWN 20 7 OPERATING AND INDICATING ELEMENTS 21 7 1 FUNCT...

Page 5: ...INFORMATION 28 9 REMOTE MONITORING 28 9 1 CONNECTING THE UPS TO THE COMPUTER 28 9 2 ASSIGNMENT OF THE RS232 INTERFACE 28 10 SPECIAL EQUIPMENT 29 10 1 ELECTRONIC STOP FUNCTION 29 11 BATTERY 30 11 1 BA...

Page 6: ...lems the reliability of the systems is our major goal since over 60 years of experience in secured power supply and techniques The scope of this manual is to describe briefly the parts that constitute...

Page 7: ...al discharging voltage is not reached 1 2 General notes regarding the ups devices The device may only be opened by trained specialists The system is to be connected up and earthed according to VDE reg...

Page 8: ...tion During normal operation the battery and the inverter are supplied with power via a rectifier online operation The change over from alternating voltage to direct voltage and back to alternating vo...

Page 9: ...means that in the case of a power failure the connected consumers will no longer be supplied with power Figure 3 Block diagram Fault in the inverter Manual bypass service bypass If there is a fault i...

Page 10: ...over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 45dB A Compass Distances Standard 600mm Reserve 450mm Environment Protectio...

Page 11: ...n mode Switch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 50dB A Compass Distances Standard 600mm Reserve 400mm Environ...

Page 12: ...tch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an distance of 1m 50dB A Compass Distances Standard 600mm Reserve 400mm Environment Prote...

Page 13: ...10s Crest Factor 3 1 Efficiency AC to AC 88 98 according to the operation mode Switch over behaviour Power failure 0ms Overload switching Automatic overload switching by the ups Noise level At an dist...

Page 14: ...Data Voltage 12V Capacity 7Ah Quantity 3 pcs Weigth each bloc 2 54kg Dimensions each bloc LxWxH 151 x 65 x 94mm Type of battery JL 205670 Battery for 2000VA UPS General Data Voltage 12V Capacity 7Ah...

Page 15: ...nt view 1000VA 1500 VA Sign Meaning ON Operation ON LINE Output Voltage available ON BAT Battery Operation BYPASS Bypass Operation FAULT UPS Failure Remark for mounting JT1000 1500 please use the cros...

Page 16: ...SPEISUNG 230V 50 60Hz MAINS INPUT 230V 50 60Hz SHOCK MOUNT L1 PE Schwingmetallpuf f er SHOCK MOUNT Abdeckplatte UPS OUTPUT 2 230V 50 60Hz COVER PLATE RS232 EARTHING BOLT M6 02 Abdeckplatte Schwingmeta...

Page 17: ...C FAULT SHOCK MOUNT BYPASS SHOCK MOUNT ON BAT ON LINE ON MOUNTING PLATE 5 3 Front view 2000 VA 3000 VA Sign Meaning ON Operation ON LINE Output Voltage available ON BAT Battery Operation BYPASS Bypass...

Page 18: ...Hz IN SHOCK MOUNT EPO N SHOCK MOUNT N RS232 USV AUSGANG 2 230V 50 60Hz NETZEINSPEISUNG 230V 50 60Hz Abdeckplatte COVER PLATE Schwingmetallpuf f er Abdeckplatte COVER PLATE 10 AMP X2 02 PE Eingangssich...

Page 19: ...f the ups 3 Set in the battery connector For transport or shipment of the ups device this connector has to be removed to prevent short circuit or fire while improper transport 4 All connecting up work...

Page 20: ...proceed as follows Switch off all consumers Press the ON OFF button in the front panel for 3 seconds An acoustic sound bleep is emitted while pressing the ON OFF button and the message Switching off s...

Page 21: ...et a parameter such as the output voltage etc The formalism is as follows Press the FUNC key on a running UPS unit for 2 seconds to start the menu for the UPS unit parameters Pressing of the ENTER but...

Page 22: ...50 2Hz Input frequency of the UPS BAT VOLT 24V Battery voltage of the battery pack O P LOAD 80 Utilisation of the UPS as a percentage O P W 700W Output in Watts O P VA 1000VA Output in VA O P CURR 2A...

Page 23: ...de If activated the UPS will switch to bypass if the preset parameters are not maintained ON OFF OFF Operating mode setting HE mode setting Online Offline mode ON OFF OFF Setting for a permanent manua...

Page 24: ...point to be altered using the key ENTER in this case HE mode The key FUNC is then used to manoeuvre through the options for the selected parameter ON OFF You have the option to select between 10 and 1...

Page 25: ...t frequency range covers the range of 45Hz 65Hz The following situation occurs where the UPS unit has a fault Before the UPS unit switches to bypass the CPU first checks to see whether the input volta...

Page 26: ...ult yourself using these trouble shooting instructions The UPS emits acoustic error signals for A mains fault the UPS unit runs in battery mode and the alarm sounds every 5 seconds Battery discharge u...

Page 27: ...red Battery operation on battery A bleep every 5 sec The UPS operates in autonomy mode loss of input mains Save your data and shut down your computer in a controlled fashion Battery charge fault charg...

Page 28: ...e UPS unit can be monitored and checked by a computer through the use of special software Switching off of the UPS unit in the case of power failure is possible 9 1 Connecting the UPS to the computer...

Page 29: ...ug Actuation of the external electronic STOP switch causes the output of the UPS unit to be switched to voltage free and the UPS unit shuts down In order to provide the consumers with a voltage again...

Page 30: ...he case of restoration of the mains power before the end of the backup time the inverter continues to run automatically until the battery is charged up Restoration of mains power after total discharge...

Page 31: ...acket is located on the left side of the battery rack 4 Unhook the retaining bracket 5 Pull the battery pack out of the UPS unit using the pulling strap Please note that if a power failure occurs now...

Page 32: ...battery The ventilation slots front and backsides of the UPS have to be clean without any dust or something soiling to prevent a reduced air exchange Please observe the necessary distance to surround...

Page 33: ...st blich Not scalable drawing Detail General tolerances Treatment Material Material thickness Surface treatment Varnishing Tool metal bender Prog no metal bender A 1 2 3 4 5 6 7 8 A B B C C D D O B k...

Reviews: