JOWA Ag-S
Silver Ion Water Treatment System
Standard
11/32
5.1.3
Final Setup
1. Adjust the flow through the chamber to approximately 3 l/min. by
adjusting the flow setting valve. The bottom of the float should
be at the 3 l/min. line. See Setup Menu section 5.4.5 to
run water through the system without producing silver ions.
2. Set up Relays if you want to have an external alarm, use a pump
to move water through the Ag-S or control another solenoid with
the power-on option.
See Setup Menu section 5.4.6
5.2
Operating the Menu System
When power is first applied to the unit the application program of the Ag-S is started.
It will search for any optional systems (such as remote Ag-S units) that are
connected. If only one unit is found it will immediately go to the Main Menu. If you
have additional equipment connected to the system then it will prompt you to connect
to a particular unit. Pick the serial number of the unit you want to control or display.
The serial number is located under the left side screw cover. See section 4.1 for
instructions on how to remove the side screw covers.
On the display, the main menu will be shown. This menu consists of a number of
screens that allow you to adjust and/or set all the system parameters such as; silver
consumption, Relays, Inputs and perform Diagnostics if the system is not operating
properly. See Section 5.4 for the complete menu structure.
You navigate in the menu system by pressing
the buttons:
Up
Down
Right
Left
Enter
On/Off
The On/Off button turns the display backlight on
or off and returns the display to either the main
menu or if treating water, to the untreated water
status or to the flow status in Direct flow mode.
The Ag-S still operates when the display is
turned off. The production of Silver Ions is
indicated when the Power LED is on steady and not flashing.