WEAK/BAD BATTERY 

The UPS automatically tests the battery’s condition. If the battery is weak, bad 
or disconnected, the  Weak/Bad Battery icon will illuminate and the Battery Ca-
pacity Bar Graph will turn off, the LCD screen will display error code E06 and 
the audible alarm will sound three beeps every five minutes until the battery is 
either reconnected or replaced.  This alarm will be repeated until the batteries 
pass a self-test.  It is recommended that the UPS be allowed to charge over-
night before performing a battery test to confirm a Weak/Bad Battery condition. 
 

OVERLOAD 

When the amount of load attached to the UPS exceeds its power rating, the 
Overload icon will illuminate, the LCD screen will display error code E02 and 
the audible alarm will sound continuously (AC and Battery modes). This alarm 
will remain on until the excess load is removed or the UPS’s self protection cir-
cuit shuts the UPS down. 
 
To clear the overload alarm when the UPS has shutdown requires that the UPS 
perform a battery test. First remove part of the load, then turn the UPS on, the 
Overload icon and the audible alarm will be on.  Second either use the Test 
Button or unplug the input power cord to perform the battery test. 

 
UPS FAULT 

When the UPS detects an internal fault, the Fault icon will illuminate and an 
error code will be displayed on the LCD screen, the audible alarm will sound 
continuously and the output will be turned off.  The fault condition, in some in-
stances, may be cleared by turning the UPS off and then on.  If the fault condi-
tion does not clear the UPS must be sent in for service.  
See the Troubleshooting section. 
 

IF THE UPS REQUIRES SERVICE

 

Use the Troubleshooting section to identify and solve simple problems. Verify 
there are no tripped circuit breakers and that the batteries are good. If you need 
to contact Juice Goose for service or assistance, do so using the information in 
this manual or www.juicegoose.com. In order to receive the best, prompt ser-
vice have the following information available: 
 

a) Personal (and Company) contact name and address. 

 

b) Reseller and purchase date.  

 

c) The model and serial number. 

 

e) Description of the issue.  

 

f) Photo image of the front panel display can be valuable.  

 

g) Description of the powered equipment including wattage ratings. 

 
A technician will help identify and work to resolve the issue. If the unit requires 
factory service you will be issued a Return Authorization (RA) Number.  
If the unit is under warranty, the repairs will be done at no charge. Otherwise 
there will be a charge for shipping and repair. 

Pack the unit in its original packaging. If the original packaging is not 
available, ask a Juice Goose representative about shipping instructions. It 
is important to pack the unit properly in order to avoid damage. Never use 
styrofoam or similar beads for a packing material.  Mark the RA Number 
on the outside of the packaging.  

Summary of Contents for SRA 07000

Page 1: ...User Guide and Product Information UPS Battery Backup Models SRA 07000 SRA 10000 SRA 15000 SRA 20000 August 2021...

Page 2: ...ion 5 Troubleshooting Getting Service 6 Replacing the Battery 7 Specifications 8 Limited Product Warranty Regulatory Compliance cTUVus Conforms to UL1778 5th Edition CSA22 2 No 107 3 14 R 2014 FCC Cla...

Page 3: ...s permettra de correctement installer le syst me pour atteindre son rendement maxi mum en toute s curit CAUTION The maximum ambient operating temperature for this UPS series is 40 C 0 40 C for Ambient...

Page 4: ...local electrical codes Do not use extension cords adapter plugs or surge strips ATTENTION Branchez l UPS sur une prise murale c a de terre bipo laire trois fils La prise de courant doit tre connect e...

Page 5: ...sassemble the UPS be yond the battery replacement procedure This UPS contains no user serviceable parts Re pairs and battery replacement must be per formed by QUALIFIED SERVICE PERSONNEL ONLY AVERTISS...

Page 6: ...s To de energize the outputs of the UPS 1 If the UPS is on press and release the On Off Test button during the audible alarm s first beep to turn the UPS off 2 Disconnect the UPS from the AC wall outl...

Page 7: ...nstructions this equipment may cause interference to radio and television reception If this equipment does cause interfer ence to radio or television reception the user is encouraged to move this equi...

Page 8: ...rat ing in the AVR voltage regulating mode The On Battery icon will illuminate when the UPS is operating in the Battery mode It will extinguish when utility power resumes and the UPS is in AC mode The...

Page 9: ...and hold the On Off Test but ton until the audible alarm sounds four beeps then release The UPS will perform a 10 second Self Test When the unit is operating in Battery mode pressing the Alarm Silence...

Page 10: ...eAlways On Battery Backup output receptacles LabeledAlways On does not support the Load Shedding Function NOTE The locking receptacle is only on the SRA20000 model 8 The option slot is for option card...

Page 11: ...life Observe the following maximum environmental conditions Operating Temperature 32F to 104F Operating Elevation above sea level 0 to 10 000 ft Relative Humidity 95 non condensing Storage Temperature...

Page 12: ...nt uniquement con us pour fixer l onduleur au rack 1 Use two or more people when installing the extremely heavy UPS 2 Remove the UPS from the shipping box and place on a flat surface NOTE No tools are...

Page 13: ...k and secure with the four retaining screws pro vided TOWER CONFIGURATION Tower brackets are provided with the UPS Use cau tion The UPS is extremely heavy NOTE Be sure to place the UPS in the tower br...

Page 14: ...t on each side of the LCD panel Insert a small flat head screwdriver into one of the small slots and gently pry the LCD outward Position the LCD panel so that it reads in the upright position Gently p...

Page 15: ...A ATTENTION Pour r duire les risques d incendie faites le raccordement uniquement sur un circuit d alimentation lectrique quip d un dispositif de protection de surintensit de circuit de d rivation de...

Page 16: ...lecommnication use Connect one end of the RJ11 cable to the EPO port and the other end of the RJ11 cable to the EPO switch In the AC or the Battery mode short pin4 to pin5 for approximately 0 5 second...

Page 17: ...t brownout or an over voltage condition occurs the UPS will transfer to the battery mode the On Battery light will illuminate and the audible alarm will sound once every ten seconds indicating that th...

Page 18: ...to support the connected load During the battery test the UPS will switch to the battery mode and the On Battery icon will illuminate and the audible alarm will sound If the UPS fails a battery test o...

Page 19: ...support the Load Shedding Function EMERGENCY POWER OFF EPO FUNCTION Connect one end of the RJ11 cable to the EPO port and the other end of the RJ11 cable to the EPO switch In the AC or the Battery mod...

Page 20: ...D screen the audible alarm will sound continuously and the output will be turned off The fault condition in some in stances may be cleared by turning the UPS off and then on If the fault condi tion do...

Page 21: ...UPS from computer cable and press On button Fault icon is on and there is a continu ous alarm sound The UPS has a fault See Error Codes in this manual Error Code E01 UPS is shut down Check attached l...

Page 22: ...batteries in a fire The batteries may explode The batteries in this UPS are recyclable Dispose of the batteries properly The bat teries contain lead and pose a hazard to the environment and human heal...

Page 23: ...ectez la source d alimentation avant de brancher ou de d brancher les bornes d une batterie 6 V rifiez si par inadvertance la batterie est toujours mise la terre Si c est le cas supprimez la source de...

Page 24: ...ugged into the output of the UPS 2 Press the On Off Test Button on the front panel to turn the UPS off 3 Unplug the UPS s AC power cord from the AC wall outlet 4 Unplug the equipment from the output r...

Page 25: ...4 Verify proper polarity Reconnect the battery connectors together NOTE Some sparking might occur this is normal 15 Re install the battery door on the UPS 16 Properly dispose of the old batteries at a...

Page 26: ...Hz 10 Low Voltage Transfer 89 VAC Return to utility power 94 VAC High Voltage Transfer 151 VAC Return to utility power 146 VAC Over Current Protection Resettable Circuit Breaker Power Cord 10 ft NEMA...

Page 27: ...ROTECTION AND FILTRATION Surge Energy Rat ing 960 Joules Surge Capacity 6500 Amps Total One Time Response Time 0 ns Normal Mode 5 ns Common Mode Surge Voltage Let Through 0 30 Of Applied Standard Surg...

Page 28: ...ical advice furnished before or after delivery in regard to use or appli cation of this equipment is furnished without charge and represents the manu facturer s best judgment under the circumstances E...

Reviews: