o
Route the bus cable towards the rear.
o
Install cover on top of the bus terminal so that it snaps into place (picture 4).
Removing the cover
picture 5: Removing the cover
o
Press the cover to the side and pull it off (picture 5).
5.2 Commissioning
Load the address and the application software
o
Switch on mains voltage.
o
Switch on the bus voltage
o
Assign physical address and note on the device label.
o
Commission DALI system using commissioning software.
i
For more detailed information on commissioning of the DALI system, see the technical
product information for this device.
o
Load the application software into the device.
i
No programming is possible if no mains voltage is connected.
6 Appendix
6.1 Technical data
Supply
Rated voltage
AC 110 ... 240 V ~
Mains frequency
50 / 60 Hz
Power loss
max. 3 W
Ambient conditions
Ambient temperature
-5 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
DALI
DALI rated voltage
DC 16 V (typical)
Number of DALI subscribers
max. 64
DALI transmission rate
1.2 kbit/s
DALI protocol
EN 60929 Annex E4
Cable type
Sheathed cable 230 V, e,g. NYM
DALI cable length
6/8
82559913
J:0082559913
16.08.2010
DALI gateway