Application
Ref. no. 2103 REG ES
Page 21
of 44
Object Name
Object
function
Type DPT
Flag
41, 64,
87, 110
Ch
n
EC Rate 2 Reset counter reading
1 bit
1.017
C-W--
Description: The counter level of the channel for Rate 2 is reset on receiving this object. The value of the
object is irrelevant here.
Object Name
Object
function
Type DPT
Flag
42, 65,
88, 111
Ch
n
EC Rate 2 Curr. count. reading
4 bytes
13.010
CR-T-
Description: The intermediate counter level of the channel for Rate 2 in
Wh
.
Object Name
Object
function
Type DPT
Flag
43 66,
89, 112
Ch
n
EC Rate 2 Reset Curr. count. reading
1 bit
1.017
C-W--
Description: The intermediate counter level of the channel for Rate 2 is reset on receiving this object. The
value of the object is irrelevant here.
Object Name
Object
function
Type DPT
Flag
44, 67,
90, 113
Ch
n
EC Rate 2 Trigger 1 Curr. count. reading
1 bit
1,017
C-W--
Description: If appropriate configured, the intermediate counter of the channel for Rate 2 is reset and
started on receiving this object. The value of the object is irrelevant here.
Object Name
Object
function
Type DPT
Flag
45, 68,
91, 114
Ch
n
EC Rate 2 Trigger 2 Curr. count. reading
1 bit
1.017
C-W--
Description: If appropriately configured, the intermediate counter level of the channel for Rate 2 is
transmitted on receiving this object. The intermediate counter is optionally stopped. The value of the
object is irrelevant here.
Object Name
Object
function
Type DPT
Flag
46, 69,
92, 115
Ch
n
EC Rate 3 Counter reading
4 bytes
13.010
CR-T-
Description: The counter level of the channel for Rate 3 in
Wh
.
Object Name
Object
function
Type DPT
Flag
47, 70,
93, 116
Ch
n
EC Rate 3 Reset counter reading
1 bit
1.017
C-W--
Description: The counter level of the channel for Rate 3 is reset on receiving this object. The value of the