Application
Ref. no. 2103 REG ES
Page 29
of 44
Description:
Values:
Comment:
Send current intensity on change (0.1
A)
0
...160
The current intensity measured on
Channel 3 can be transmitted on
changes.
Setting of the current intensity change,
at which the measured current intensity
is transmitted, or switch-off of this
function with the value 0.
Send effective power on change (W)
0
...4240
The effective power measured on
Channel 3 can be transmitted on
changes.
Setting of the effective power change,
at which the measured effective power
is transmitted, or switch-off of this
function with the value 0.
Telegram on limit value (effective
power)
Yes
No
Here, it is possible to set whether a
telegram is transmitted when a limit
value of the effective power measured
on Channel 3 is over or undershot.
Accept
limit value from bus
Volatile
Permanent
The limit value for the effective power
measured on Channel 3 can be
overwritten with an object.
Setting of whether the new limit value
applies until the next reset / bus voltage
failure or permanently overwrites the
value configured with the ETS.
Limit value (W)
0
..4240
Specification
of
the limit value for the
effective power measured on
Channel 3.
Hysteresis (W)
0
..4240
A hysteresis can be configured for the
over or undershooting of a limit value of
the effective power measured on
Channel 3. On overshooting, the actual
limit value is
Limit value +
½
hysteresis
and, on undershooting,
Limit value -
½
hysteresis.
Specification of the hysteresis for the
effective power measured on
Channel 3.
Send reactive power on change (W)
0
...4240
The reactive power measured on
Channel 3 can be transmitted on
changes.
Setting of the reactive power change, at
which the measured effective power is
transmitted, or switch-off of this function
with the value 0.