Removing the cover 

Figure 6: Removing the cover 

Press the cover to the side and pull it off (figure 6). 

4.2 Commissioning 

Load the address and the application software 

Switch on the bus voltage. 

Assign physical address. 

Load the application software into the device. 

Note the physical address on the device label. 

5 Appendix 

5.1 Technical data 

Binary input 4-gang, 230 V, Art. No.  2114 REG

Mark of approval 

VDE 

KNX 
KNX medium 

TP 1 

Commissioning mode 

S-mode 

Rated voltage KNX 

DC 21 ... 32 V SELV 

Power consumption KNX 

max. 150 mW 

Connection type for bus 

Connection terminal 

Ambient temperature 

-5 ... +45 °C 

Storage/transport temperature 

-25 ... +70 °C 

Inputs 
Rated voltage 

AC 110 ... 230 V ~ 

Signal level "0" signal 

AC 0 ... 70 V ~ 

Signal level "1" signal 

AC 90 ... 253 V ~ 

Mains frequency 

50 / 60 Hz 

Input current at nominal voltage 

approx. 7 mA 

Signal duration 

min. 200 ms 

Signal delay 
rising edge 

approx. 2 ms 

falling edge 

approx. 40 ms 

Housing 
Fitting width 

36 mm / 2 modules 

Power loss 

max. 1.7 W 

5/7 

82540413 
J:0082540413 

06.08.2013 

Binary input 

Summary of Contents for 2114 REG

Page 1: ...killed persons Failure to observe the instructions may cause damage to the device and result in fire and other hazards Danger of electric shock Do not connect FELV and SELV PELV systems together When...

Page 2: ...out with the aid of KNX certified software The latest versions of product database and the technical descriptions are available on our website Intended use Polling of conventional switching or push b...

Page 3: ...tal Before carrying out work on the device or load disengage all the corresponding circuit breakers Cover up live parts in the working environment Fitting the device Observe the temperature range Ensu...

Page 4: ...4 Common reference potential for inputs E1 E3 and E4 E6 Installing the cover It is necessary to install a cover to protect the bus connection against hazardous voltages in the connection area Figure 5...

Page 5: ...oval VDE KNX KNX medium TP 1 Commissioning mode S mode Rated voltage KNX DC 21 32 V SELV Power consumption KNX max 150 mW Connection type for bus Connection terminal Ambient temperature 5 45 C Storage...

Page 6: ...modules Power loss max 3 4 W Connection single stranded 0 5 4 mm finely stranded without conductor sleeve 0 5 4 mm finely stranded with conductor sleeve 0 5 2 5 mm Cable length max 100 m Binary input...

Page 7: ...gress We provide a warranty as provided for by law Please send the device with a description of the defect to our central customer service office ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schalksm...

Reviews: