Removing the cover
Figure 6: Removing the cover
o
Press the cover to the side and pull it off (figure 6).
4.2 Commissioning
Load the address and the application software
o
Switch on the bus voltage.
o
Assign physical address.
o
Load the application software into the device.
o
Note the physical address on the device label.
5 Appendix
5.1 Technical data
Binary input 4-gang, 230 V, Art. No. 2114 REG
Mark of approval
VDE
KNX
KNX medium
TP 1
Commissioning mode
S-mode
Rated voltage KNX
DC 21 ... 32 V SELV
Power consumption KNX
max. 150 mW
Connection type for bus
Connection terminal
Ambient temperature
-5 ... +45 °C
Storage/transport temperature
-25 ... +70 °C
Inputs
Rated voltage
AC 110 ... 230 V ~
Signal level "0" signal
AC 0 ... 70 V ~
Signal level "1" signal
AC 90 ... 253 V ~
Mains frequency
50 / 60 Hz
Input current at nominal voltage
approx. 7 mA
Signal duration
min. 200 ms
Signal delay
rising edge
approx. 2 ms
falling edge
approx. 40 ms
Housing
Fitting width
36 mm / 2 modules
Power loss
max. 1.7 W
5/7
82540413
J:0082540413
06.08.2013
Binary input