Mount enclosed guide blade (11) in the fields provided next to the connection (7). 

i

If mounted on a mast without the guide blade, no correct wind direction measurement is
possible due to the resulting turbulences.

o

Route the power supply line through the mast.

o

Attach the 7-pin plug to the connection (7). Tighten threaded ring with max. 0.5 Nm.

o

Mount weather station onto the mast and align. The grub screw (2) must be pointing north.

o

Tighten grub screw (2) with max. 0.6 Nm.

Mounting weather station with fastening arm on mast or wall

Figure 7: Mounting with fastening arm

Mount enclosed fastening arm onto a suitable mast or wall. 
The enclosed hose clamps are suitable up to a maximum mast diameter of 60 mm.

i

If mounted on the supplied fastening arm, do not mount the enclosed guide blade. 

o

Mast mounting: Attach fastening arm to mounting mast using the enclosed hose clamps. 

o

Wall mounting: Attach fastening arm to the wall through the boreholes (figure 8) using
suitable screws. 

o

Route the power supply line along the underside of the fastening arm and guide the 7-pin
plug through the open pipe socket at the end of the fastening arm.

o

Attach the 7-pin plug to the connection (7). Tighten threaded ring with max. 0.5 Nm.

o

Mount weather station onto the mast and align. The grub screw must be pointing north.

o

Tighten grub screw with max. 0.6 Nm.

o

Route the power supply line through the cable bushing into an installation pipe. 

5/9

82590103
J:0082590103

30.01.2015

Universal weather station

Summary of Contents for 2225 WS U

Page 1: ...and fitted by electrically skilled persons Serious injuries fire or property damage possible Please read and follow manual fully These instructions are an integral part of the product and must remain...

Page 2: ...evaluation of weather data Wind speed Wind direction Precipitation Brightness Global radiation Twilight Temperature Relative air humidity and Air pressure Installation on the outside of buildings pref...

Page 3: ...1 Fitting and electrical connection Selecting the installation location Figure 3 Minimum distance to surfaces Figure 4 Avoid spray water 3 9 82590103 J 0082590103 30 01 2015 Universal weather station...

Page 4: ...weather station will be accessible In the case of flat roofs locate the weather station as close to the centre of the roof as possible Minimum distance to surfaces below the weather station 0 6 m fig...

Page 5: ...se clamps are suitable up to a maximum mast diameter of 60 mm i If mounted on the supplied fastening arm do not mount the enclosed guide blade o Mast mounting Attach fastening arm to mounting mast usi...

Page 6: ...24 V brown GND i The sensor head is translucent Therefore do not stick or write on the sensor head Aligning the device Figure 9 Orienting the weather station o Align the sensor head in the appropriate...

Page 7: ...ical data Supply Rated voltage AC 24 V SELV 10 Rated voltage DC 21 32 V SELV Current consumption 100 400 mA dependent on the weather Protection class III Connection cable Cable type LiYCY 4xAWG26 Cabl...

Page 8: ...g range 300 1100 hPa Resolution 0 01 hPa Accuracy 0 5 hPa 20 C Humidity sensor Measuring range 0 100 rel humidity Resolution 0 1 rel humidity Accuracy 10 rel humidity 20 C abs humidity 0 400 g m Resol...

Page 9: ...mestra e 1 58579 Schalksm hle Telefon 49 23 55 8 06 0 Telefax 49 23 55 8 06 2 04 kundencenter jung de www jung de Service Center Kupferstr 17 19 44532 L nen Germany 9 9 82590103 J 0082590103 30 01 201...

Reviews: