background image

eNet radio dimming actuator 1-gang mini

eNet radio dimming actuator 1-gang mini
Art. no.: FMUD20250UP

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Danger of electric shock. Always disconnect before carrying out work on the device or load. In
so doing, take all the circuit breakers into account, which support dangerous voltages to the
device and or load.

Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load
is not electrically isolated from the mains even when the device is switched off.

Risk of destruction if the set operating mode and load type do not match. Set correct operating
mode when connecting or exchanging the load.

Fire hazard. For operation with inductive transformers, each transformer must be fused on the
primary side in accordance with the manufacturer's instructions. Only safety transformers ac-
cording to EN 61558-2-6 may be used.

These instructions are an integral part of the product, and must remain with the end customer.

2

Intended use

Switching and dimming of lighting

Operation with suitable radio transmitters

Mounting in appliance box according to DIN 49073 in combination with a suitable cover

Installation in surface-mounted housing or panel-mounted housing (accessories) for sus-
pended ceilings

Product characteristics

Switch-on via bulb-preserving soft start

Switch-on brightness can be saved permanently

Minimum brightness can be saved permanently

Scene operation possible

Status indication with LED

Status feedback to radio transmitter

Switchable with Prog. button

Electronic short-circuit protection with permanent switch-off after 7 seconds at the latest

Electronic over-temperature protection

Automatic or manual setting of the dimming principle suitable for the load

Power extension possible by means of power boosters

Can be set with eNet server:

Maximum brightness

Dimming speed

Switch-on delay / switch-off delay

Dim up/dim down ramp

Switch-off warning

Operation locks

Continuous on, Continuous off

Hotel function

Run-on time

1 / 16

82580733

14.10.2019

J0082580733

Summary of Contents for FM J 50700 UP

Page 1: ...ty transformers ac cording to EN 61558 2 6 may be used These instructions are an integral part of the product and must remain with the end customer 2 Intended use Switching and dimming of lighting Ope...

Page 2: ...er operation and signalling could vary from what is de scribed here 4 Information for electrically skilled persons 4 1 Fitting and electrical connection DANGER Mortal danger of electric shock Before c...

Page 3: ...nsformers for halogen or LED lamps HV LED leading edge phase control Setting for incandescent lamps HV halogen lamps elec tronic transformers with halogen or LED lamps that can be dimmed according to...

Page 4: ...than 4 seconds The status LED 4 flashes after 3 seconds The actuator is in programming mode for approx 1 minute Switch radio transmitter to programming mode see radio transmitter instructions Trigger...

Page 5: ...for approx 5 seconds The actuator is reset to default setting Setting the minimum brightness The minimum brightness can be set within a range of approx 1 67 if e g the light flickers at low brightnes...

Page 6: ...dissipation Operate inductive transformers with at least 85 nominal load For ohmic inductive mixed load maximum 50 proportion of ohmic load Otherwise in correct calibration of the dimmer may result P...

Page 7: ...smitters and the Prog button are ignored Continuous off The output switches to con tinuously Off All operations of radio transmitters and the Prog button are ignored Advanced device settings Parameter...

Page 8: ...on after a delay Repeated switch on commands restart the delay time If the load has not yet been switched on due to the delay when a switch off com mand comes then the load will remain off Note The s...

Page 9: ...r remain on perman ently but only for the length of the run on time The run on time is restarted if actuation is repeated This parameter is directly connected to the Manual switch off of run on time p...

Page 10: ...l LED trailing edge phase con trol Leading edge phase control Trailing edge phase control Basic setting Universal Specifies the dimming prin ciple for the selected output Universal Automatic calibrati...

Page 11: ...value is above the set maximum brightness or below the minimum bright ness then the system will switch to the appropriate limit value Behaviour after the end of the disabling function On Off no chang...

Page 12: ...Basic setting 2 Specifies the priority for recall ing and removing a scene of type Restraint for the channel Activate forced operation brightness value 0 100 Basic setting 100 Defines the behaviour o...

Page 13: ...n is 0 Switch off brightness over shoot On Off Basic setting On Allows automatic switch off according to the brightness If the parameter is On then the light controller switches off automatically when...

Page 14: ...Check manufacturer s instructions Exchange lamps for another type Cause 2 Dimming principle and lamps do not optimally match Check operation in another dimming principle reduce connected load as well...

Page 15: ...current Cause 5 load failure Check load replace lamp For inductive transformers check primary fuse and replace if necessary Lamps flicker or buzz proper dimming not possible device buzzes Cause 1 Inco...

Page 16: ...dimming actuator 1 gang mini ALBRECHT JUNG GMBH CO KG Volmestra e 1 58579 Schalksm hle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 16 16 82580733 14 10 2019...

Reviews: