background image

eNet radio switch/push-button actuator in SCHUKO housing

Parameters

Setting options, Basic setting

Explanations

Repeater mode

On, Off
Basic setting: Off

In addition to its other func-
tions, the device can be used
as a repeater. In the "On" set-
ting, the device repeats all the
received telegrams.

Channel settings

Parameters

Setting options, Basic setting

Explanations

Switch-on delay

0 s … 24 h
Basic setting: 0 s

The load switches on after a
delay. Repeated switch-on
commands restart the delay
time. If the load has not yet
been switched on due to the
delay when a switch-off com-
mand comes, then the load
will remain off. 
In Flashing operating mode,
the pause time is set using
this parameter.
Comment: The set times apply
to operation using radio trans-
mitters. The relay is switched
immediately when the Prog
button is pressed.

Switch-off delay

0 s … 24 h
Basic setting: 0 s

The load switches off after a
delay. Repeated switch-off
commands restart the delay
time. If the load has not yet
been switched off due to the
delay when a switch-on com-
mand comes, then the load
will remain on.
In Flashing operating mode,
the pulse times are set using
this parameter.
Comment: The set times apply
to operation using radio trans-
mitters. The relay is switched
immediately when the Prog
button is pressed.

Run-on time

0 s … 24 h
Basic setting: 0 s

As soon as a run-on time has
been entered, the actuator will
no longer remain on perman-
ently, but only for the length of
the run-on time. The run-on
time is restarted if actuation is
repeated. This parameter is
directly connected to the
"Manual switch-off of run-on
time" parameter. 
Comment: The set times apply
to operation using radio trans-
mitters. The relay is switched
immediately when the Prog
button is pressed.

6 / 10

82592223

15.12.2020

J0082592223

Summary of Contents for FMAS10ZS

Page 1: ...ains voltage may be present on the load because only 1 pole is switched off Adapter plugs may not be connected in series and must be easily accessible The radio communication takes place via a non exclusively available transmission path and is therefore not suitable for safety related applications such as emergency stop and emergency call These instructions are an integral part of the product and ...

Page 2: ...date of the device software Reading of error memory Behaviour after mains voltage return The response after mains voltage return can be configured with the eNet server Default setting Off 4 Operation When operating with the eNet Server operation and signalling could vary from what is de scribed here Operation with radio transmitters Operation is with radio transmitters please observe the radio tra...

Page 3: ...sful All the memory locations in the actuator or radio transmitter are occupied All On and All Off buttons of a radio transmitter are connected to the actuator automatic ally as soon as the first connection to the radio transmitter takes place Scene buttons must be connected separately Disconnecting connection to a radio transmitter Carry out the same steps as when connecting see Connecting actuat...

Page 4: ... transformers 1500 W Inductive transformers 1000 VA HV LED lamps typ 500 W Compact fl lamp typ 500 W Fluorescent lamps uncompensated 920 VA Capacitive load 690 VA 560 μF Dimensions W H D 57 142 78 mm Radio frequency 868 0 868 6 MHz Transmission capacity max 20 mW Transmitting range in free field typ 100 m Receiver category 2 7 Parameter list The device parameters can be changed with the eNet serve...

Page 5: ...ed flashing Switch on starts flashing and switch off stops flashing The default flash frequency is 1 Hz This frequency is also the maximum flash frequency The flash frequency can be changed using parameters The parameter Switch off delay is used for the pulse time and the parameter Switch on delay for the pause time Continuous on The output switches to con tinuously On All operations of radio tran...

Page 6: ...ely when the Prog button is pressed Switch off delay 0 s 24 h Basic setting 0 s The load switches off after a delay Repeated switch off commands restart the delay time If the load has not yet been switched off due to the delay when a switch on com mand comes then the load will remain on In Flashing operating mode the pulse times are set using this parameter Comment The set times apply to operation...

Page 7: ...ters Setting options Basic setting Explanations Operating mode Switching operation Push button operation flashing Continuous on Continuous off Basic setting Switching oper ation See Device and channels Manual commissioning On Off Basic setting On Blocks manual commissioning for the device channel In the Off setting the device can not be reset to the factory set ting Local Operation On Off Basic se...

Page 8: ...Activate lock out protection switching state On Off Basic setting Off Defines the behaviour of the output on activating the lock out protection Deactivate lock out protection switching state On Off Basic setting Off Defines the behaviour of the output on deactivating the lock out protection Only vis ible when the priority for the lock out protection is 0 Priority restraint 0 4 Basic setting 2 Spec...

Page 9: ... removing a scene of type Twilight for the channel Activate twilight switching state On Off Basic setting On Defines the behaviour of the output on activating the twi light function Deactivate twilight switching state On Off Basic setting Off Defines the behaviour of the output on deactivating the twi light function Only visible when the priority for the twi light function is 0 Switch off brightne...

Page 10: ... channel selection in the Information window the following settings can be made or val ues displayed Display value Explanations Load state The load can be switched on or off Restraint Display of forced position status Operating hours Display of the operating hours since the last restart in the Settings window Einstellungen 8 Conformity Hereby Albrecht Jung GmbH Co KG declares that the radio system...

Reviews: