Universal dimming actuator, 1-gang
Installation or commissioning error. Disconnect device and luminaire, switch off circuit
breaker.
Check installation and correct.
If the wrong dimming principle has been preselected: Set correct dimming principle.
If dimming actuator calibrates itself incorrectly, e.g. with highly inductive mains or long
load cables: preselect correct dimming principle with commissioning.
LED lamp is dimly lit when dimmer is switched off
Cause: LED lamp is not optimally suited for this dimmer.
Use a compensation module, see accessories.
Use another type of LED lamp or an LED lamp of another manufacturer.
7
Accessories
External sensor
Condensation sensor
Leakage sensor
8
Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.