Art.-No.: 4071.0x LED, 4072.0x LED
Art.-No.: 8471.0x LED W, 8472.0x LED W
4.2.3 Object table
Number of communication objects:
Depends on the device variant and the set
function.
max. 10 (largest object number: 17)
Number of addresses (max):
100
Number of assignments (max):
100
Dynamic table management
No
Maximum table length
---
Objects for "switching"
Function:
Switching
Object
h
0, 2
Function
Switching
Name
Rocker 1-2
1
Type
1-bit
DPT
1.xxx
Flag
C, W, T
Description
1-bit object for transmission of switching telegrams (ON, OFF). This object is
only visible with rocker functions.
Function:
Switching
Object
h
0, 1,
2, 3
Function
Switching
Name
Button 1-4
1
Type
1-bit
DPT
1.xxx
Flag
C, W, T
Description
1-bit object for transmission of switching telegrams (ON, OFF). This object is
only visible with button functions.
Objects for "dimming"
Function:
Switching
Object
h
0, 2
Function
Switching
Name
Rocker 1-2
1
Type
1-bit
DPT
1.xxx
Flag
C, W, T
Description
1-bit object for transmission of switching telegrams (ON, OFF). This object is
only visible with rocker functions.
Function:
Dimming
Object
h
8, 10
Function
Dimming
Name
Rocker 1-2
1
Type
4-bit
DPT
3.007
Flag
C, W, T
Description
4-bit object for relative brightness adjustment between 0% and 100 %. This
object is only visible with rocker functions.
1: The number of rockers or buttons depends on the planned device variant.
Page 15 of 34
Software "10Fx11"
Object table