Art.-No.: 4071.0x LED, 4072.0x LED
Art.-No.: 8471.0x LED W, 8472.0x LED W
Reduce brightness by
1.5 %
3 %
6 %
12.5 %
25 %
50 %
100 %
This parameter sets the relative
dimming level when the brightness is
reduced. On each long operation, the
brightness is changed at maximum by
the configured level.
Time between switching
and dimming
300 ms
400 ms
500 ms
700 ms
1s
This parameter defines how long the
rocker switch must be pressed for the
device to transmit a dimming telegram
(time for long button-press).
Transmit stop telegram?
Yes
No
On "Yes" the device transmits a
telegram for stopping the dimming
process when the rocker is released.
When the device transmits telegrams for
dimming in small steps, the stop
telegram is generally not needed
(setting: "No").
Telegram
repeat?
Yes
No
This parameter can be used to activate
telegram repetition for dimming. With the
rocker switch held down at the top or
bottom, the pushbutton sensor will then
transmit the relative dimming telegrams
(in the programmed level width) until the
rocker/button is released again.
Time between two
telegrams
200 ms
300 ms
400 ms
500 ms
750 ms
1 sec
2 sec
This parameter defines the interval at
which the dimming telegrams are
automatically repeated in the telegram
repetition mode.
This parameter is visible only if
"Telegram repetition ? = Yes"!
With "Venetian blind" function...
Command on pressing
rocker
Rocker up: UP /
Rocker down: DOWN
Rocker up: DOWN /
Rocker down: UP
Defines the command when the rocker
switch is pressed at the top and at the
bottom.
Time between short-
time and long-time
command
300 ms
400 ms
500 ms
This parameter defines the time
between a short-time and a long-time
telegram.