Art.-No.: 4071.0x LED, 4072.0x LED
Art.-No.: 8471.0x LED W, 8472.0x LED W
6 %
12.5 %
25 %
50 %
100 %
increased. During each long operation,
the brightness is changed at maximum
by the configured level.
Reduce brightness by
1.5 %
3 %
6 %
12.5 %
25 %
50 %
100 %
This parameter sets the relative
dimming level when the brightness is
reduced. During each long operation,
the brightness is changed at maximum
by the configured level.
Time between switching
and dimming
300 ms
400 ms
500 ms
700 ms
1s
This parameter defines how long the
rocker switch must be pressed for the
device to transmit a dimming telegram
(time for long button-press).
Transmit stop telegram?
Yes
No
On "Yes" the device transmits a
telegram for stopping the dimming
process when the button is released.
When the device transmits telegrams for
dimming in small steps, the stop
telegram is generally not needed
(setting: "No").
Telegram
repeat?
Yes
No
This parameter can be used to activate
telegram repetition for dimming. With the
button held down, the device will then
transmit the relative dimming telegrams
(in the programmed level width) until the
button is released again.
Time between two
telegrams
200 ms
300 ms
400 ms
500 ms
750 ms
1 sec
2 sec
This parameter defines the interval at
which the dimming telegrams are
automatically repeated in the telegram
repetition mode.
This parameter is visible only if
"Telegram repetition ? = Yes"!
With "Venetian blind" function...
Command on pressing
the button
No reaction
UP
DOWN
Defines the command when a button is
pressed.
Page 29 of 34
Software "10Fx11"