Figure 4: Connection diagram with multiple power boosters 

(1)  Power booster 
(3)  Dimmer 
(4)  Local extension 

Pay attention to the necessary cable cross-section of the common power cable. 

If multiple power boosters are used, add up the minimum loads of all the separate devices. 

In the case of lighting systems with an output of over 3500 W/VA, the installation must be 
distributed across two miniature circuit breakers with the same conductor. 

Connect the power booster according to the connection diagram, connection diagram with 
RMD dimmer (figure 2), connection diagram with FM dimmer (figure 3) or connection 
diagram with multiple power boosters (figure 4). 

If multiple circuit breakers supply dangerous voltages to the device or load, couple the 
circuit breakers to ensure tripping. 

Calculation example for the number of power boosters required: 

P

Load to be dimmed, e.g. 2200 W 

P

Max. dimmer load, e.g. 500 W 

P

LZ 

Max. universal power extension load, e.g. B. 
500 W 

P

LZG 

Power that the power boosters have to provide 

Number of power boosters required 

Calculation of the load to be covered by power boosters:
P

L

 - P

D

 = P

LZG

P

LZG

 = 2200 W - 500 W = 1700 W 

Number of power power boosters:
P

LZG

 / 

PLZ

 = n

n = 1700 / 500 = 3.4  
4 power boosters are required for the loads assumed in the example. 

5 Appendix 

5.1 Technical data 

Rated voltage 

AC 230 V ~ 

Mains frequency 

50 / 60 Hz 

Ambient temperature 

+5 ... +45 °C 

4/7 

82557263 
J:0082557263 

27.02.2013 

Light Management  

Universal amplifier for rail mounting 200-500 W 

Summary of Contents for ULZ 1215 REG

Page 1: ...re hazard For operation with inductive transformers each transformer must be fused on the primary side in accordance with the manufacturer s instructions Only safety transformers according to EN 61558 2 6 may be used A minimum power of 10 kVA is required for operation on isolating transformer networks Otherwise it is not ensured that the dimmer will correctly recognise the dimming principle suitab...

Page 2: ... represent any defect in the device i Brightness differences between the lighting on a dimmer without powerpower booster and a dimmer with power booster are possible 4 Information for electrically skilled persons 4 1 Fitting and electrical connection DANGER Electrical shock when live parts are touched Electrical shocks can be fatal Before carrying out work on the device or load disengage all the c...

Page 3: ...Figure 2 Connection diagram with RMD dimmer Figure 3 Connection diagram with FM dimmer 3 7 82557263 J 0082557263 27 02 2013 Light Management Universal amplifier for rail mounting 200 500 W ...

Page 4: ...r boosters figure 4 o If multiple circuit breakers supply dangerous voltages to the device or load couple the circuit breakers to ensure tripping Calculation example for the number of power boosters required PL Load to be dimmed e g 2200 W PD Max dimmer load e g 500 W PLZ Max universal power extension load e g B 500 W PLZG Power that the power boosters have to provide n Number of power boosters re...

Page 5: ...esult capacitive inductive not permitted Minimum connected load 200 W VA Power reduction per 5 C in excess of 45 C 15 Connection single stranded max 4 mm finely stranded with conductor sleeve 0 5 2 5 mm finely stranded without conductor sleeve 0 75 4 mm Number of power boosters see reference list Total length power cable max 100 m Fitting width 36 mm 2 modules Figure 5 Reference list of convention...

Page 6: ...om mains switch off circuit breakers Let system cool down for approx 15 minutes Check the installation situation Reduce the connected load Switch circuit breakers and system on again i Load is initially distributed to the remaining devices The further behaviour of the system depends on the dimmer used and the number utilisation and installation situation of the devices 5 3 Warranty We reserve the ...

Page 7: ...chalksmühle Telefon 49 23 55 8 06 0 Telefax 49 23 55 8 06 2 04 kundencenter jung de www jung de Service Center Kupferstr 17 19 44532 Lünen Germany 7 7 82557263 J 0082557263 27 02 2013 Light Management Universal amplifier for rail mounting 200 500 W ...

Reviews: