Chapter 2.

3

Site Preparation

The appliance should be installed in a rack housed in a dry, clean, well-ventilated, and temperature-controlled
environment.
• The site should be as dust-free as possible, because dust can clog air intake vents and filters, reducing the

efficiency of the appliance cooling system.

• Maintain ambient airflow for normal appliance operation. If the airflow is blocked or restricted, or if the intake

air is too warm, the appliance might overheat, causing the appliance temperature monitor to power off the
appliance to protect the hardware components.

The MWS1000 environmental requirements are:
• Ambient temperature for normal operation: 41°F to 104°F (5°C to 40°C)

• Ambient temperature for storage: -40°F to 158°F (-40°C to 70°C)

• Relative humidity, operating: 8% to 90% non-condensing

• Relative humidity, storage: 5% to 95% non-condensing

• Maximum operating altitude: 10,000 feet (3000 m)

2.1. Clearance Requirements for Airflow and Hardware

Maintenance for MWS1000

When planning the installation site, allow sufficient clearance around the rack. For the cooling system to
function properly, the airflow around the chassis must be unrestricted.
• Allow at least 6 in. (15 cm) of clearance on the side between devices that have fans or blowers installed.

• Allow 2.8 in. (7 cm) between the side of the chassis and any non-heat-producing surface such as a wall.

• Ensure that the airflow vents in the front and rear panels remain open and uncovered for proper cooling.

• For service personnel to remove and install hardware components, there must be adequate space at the

front and back of the appliance. At least 24 in (60 cm) is required both in front of and behind the chassis.
The front of the chassis extends approximately 0.5 in (1.3 cm) beyond the mounting ears.

2.2. Power Specifications

An AC power supply is standard. A DC power supply is an available option.
• AC input voltage: 100 VAC to 240 VAC

• AC input line frequency: 47 Hz/63 Hz nominal

• AC system current rating: 4.0 A max

• AC minimum efficiency: 88%

• DC input voltage: -40 VDC to -72 VDC

• DC system current rating: 20 A max

• DC minimum efficiency: 88%

Summary of Contents for MWS1000

Page 1: ...Mykonos Web Security 4 95 8 Hardware Guide...

Page 2: ...Mykonos Web Security 4 95 8 Hardware Guide This document contains a specification for the MWS1000 hardware appliance as well as instructions for installation into a server environment...

Page 3: ...on 3 2 1 Clearance Requirements for Airflow and Hardware Maintenance for MWS1000 3 2 2 Power Specifications 3 2 3 Unpacking and Inspecting the MWS1000 4 2 4 Before You Install MWS1000 4 3 Installing M...

Page 4: ...n High Availability deployments USB interface One USB port Processor Dual Quad core Intel E5620 2 4Ghz RAM 48 GB DDR3 Storage Six storage drive slots Fans Three 40 mm fans Power supplies Removable AC...

Page 5: ...he MWS1000 has an Input Output Controller with two 10 Gb RJ 45 Ethernet ports labeled 0 and 1 Depending on your order configuration the front panel drive bays may or may not be configured The MWS1000...

Page 6: ...e Maintenance for MWS1000 When planning the installation site allow sufficient clearance around the rack For the cooling system to function properly the airflow around the chassis must be unrestricted...

Page 7: ...ch unit 10 Document any damage noted during your inspection 11 Confirm that the platform has the correct number and type of modules for your ordered configuration If you detect or suspect damage to an...

Page 8: ...only copper grounding conductors For a ground wire attaching directly to the rack we recommend using the following ground lug Panduit P N LCDX8 10A L 8 AWG 10 stud 0 625 inch spacing To ensure a reli...

Page 9: ...0GbE cable into port 0 or 1 on the 10GbE NIC They will be configured as eth4 and eth5 in the setup respectively 10 Power on the appliance When you turn on the power the internal port uses its two LEDs...

Page 10: ...s maintain the proper polarity The power source cables may be labeled and to indicate their polarity There is no standard color coding for DC power cables The color coding used by the external DC powe...

Page 11: ...3 3 RJ 45 Console Connector Pinout Table 3 1 RJ 45 Console Connector Pinout reference Pin Description 1 RTS Output Request to Send 2 DTR Output Data Terminal Ready 3 TxD Output Transmit Data 4 GND Cha...

Reviews: