Table 57: Setting the JNP10K-PWR-AC2 Dip Switches
Field
State
Switch
INP1 (INP0 in CLI output) is present
On
1
INP1 is not present
Off
INP2 (INP1 in CLI output) is present
On
2
INP2 is not present
Off
Enabled for 30 A feed; 5500-W for a single feed, 5000-W for dual feeds
On
3
Enabled for 20 A feed; power supply capacity is 3000-W
Off
15. Verify that the INP1 and INP2 LEDs on the power supply faceplate are lit and are on steadily.
16. Press the power switch to the on (|) position.
How to Remove a JNP10K-PWR-DC Power Supply
The JNP10K-PWR-DC power supply in an MX10008 and in an MX10016 chassis is a hot-removable and
hot-insertable field-replaceable unit (FRU). You remove DC power supplies from the rear of the chassis.
CAUTION:
Before you remove a power supply, ensure that sufficient power supplies
are left in the chassis to power the router (see Power Requirements for MX10008
Components).
WARNING:
Before performing DC power procedures, ensure that power is removed
from the DC circuit. To ensure that all power is off, locate the circuit breaker on the panel
board that services the DC circuit, router the circuit breaker to the OFF position, and
tape the router handle of the circuit breaker in the OFF position.
Before you remove a DC power supply from the router:
215
Summary of Contents for MX10008
Page 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Page 19: ......
Page 89: ......
Page 129: ......
Page 170: ......
Page 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Page 279: ......
Page 287: ......
Page 318: ...Restricted Access Warning 321 ...
Page 333: ...Jewelry Removal Warning 336 ...
Page 336: ...Operating Temperature Warning 339 ...
Page 345: ...DC Power Disconnection Warning 348 ...
Page 349: ...DC Power Wiring Sequence Warning 352 ...
Page 352: ...DC Power Wiring Terminations Warning 355 ...
Page 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...