Removing an MX10008 Fan Tray Controller | 186
Installing an MX10008 Fan Tray Controller | 188
An MX10008 router has two independent, field-replaceable fan trays. Fan trays must be replaced within
the duration mentioned in
.
Table 56: Replacement Duration for the Fan Tray
Duration
Chassis Ambient Temperature
5 minutes
27°C
3 minutes
35°C
2 minutes
40°C
NOTE:
When replacing the fans or SFBs at 40°C chassis ambient temperature, ensure that the
fans run at 100% fan speed for at least 10 minutes before replacing the fans or SFBs.
Use the test chassis fan tray 0 speed minutesfull-speed and test chassis fan tray 1 speed full-speed
commands to set the chassis fans to 100% speed.
To install or remove the fan trays and fan tray controller, see the following sections:
Removing an MX10008 Fan Tray
An MX10008 has two independent, field-replaceable fan trays. Each fan tray is a hot-removable and
hot-insertable field-replaceable unit (FRU); you can remove and replace the fan tray while the router is
running without turning off power to the router or disrupting routing functions. There are two models of
the fan tray, JNP10008-FAN and JNP10008-FAN2.
CAUTION:
Do not remove the fan tray unless you have a replacement fan tray available.
Each fan tray is installed vertically on the rear, or FRU-side, of the chassis.
179
Summary of Contents for MX10008
Page 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Page 19: ......
Page 89: ......
Page 129: ......
Page 170: ......
Page 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Page 279: ......
Page 287: ......
Page 318: ...Restricted Access Warning 321 ...
Page 333: ...Jewelry Removal Warning 336 ...
Page 336: ...Operating Temperature Warning 339 ...
Page 345: ...DC Power Disconnection Warning 348 ...
Page 349: ...DC Power Wiring Sequence Warning 352 ...
Page 352: ...DC Power Wiring Terminations Warning 355 ...
Page 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...