Table 30: Rack Requirements for the MX10008 (continued)
Guidelines
Rack Requirement
•
Secure the rack to the building structure.
•
If earthquakes are a possibility in your geographical area, secure the
rack to the floor.
•
Secure the rack to the ceiling as well as to the wall or floor for
maximum stability.
Rack connection to building structure
SEE ALSO
MX10008 Chassis Physical Specifications | 36
Rack-Mounting and Cabinet-Mounting Warnings | 323
MX10008 Clearance Requirements for Airflow and Hardware Maintenance | 98
Mounting an MX10008 in a 4-Post Rack Using a Mechanical Lift | 143
Manually Mounting an MX10008 in a 4-Post Rack | 147
MX10008 Clearance Requirements for Airflow and Hardware Maintenance
When planning the site for an MX10008 router installation, you must allow sufficient clearance around
the installed chassis for cooling and maintenance (see
for MX10008.
NOTE:
A minimum of half-an-inch clear space from the bottom of the chassisis is required for easy
removal and insertion of the fan tray.
98
Summary of Contents for MX10008
Page 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Page 19: ......
Page 89: ......
Page 129: ......
Page 170: ......
Page 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Page 279: ......
Page 287: ......
Page 318: ...Restricted Access Warning 321 ...
Page 333: ...Jewelry Removal Warning 336 ...
Page 336: ...Operating Temperature Warning 339 ...
Page 345: ...DC Power Disconnection Warning 348 ...
Page 349: ...DC Power Wiring Sequence Warning 352 ...
Page 352: ...DC Power Wiring Terminations Warning 355 ...
Page 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...