Figure 13: Connecting the Grounding Cable
g036091
6.
Verify that the grounding cabling is correct, that it does not touch or block access
to device components, and that it does not drape where people could trip on it.
Connect Power to an AC-Powered Services Gateway
WARNING:
The device must be properly grounded before you connect the AC power
cords.
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and
connect the strap to one of the ESD points on the chassis. For more information
about ESD, see the
SRX 3400 Services Gateway Hardware Guide
.
2.
Locate the power cord or cords you will use to connect the device to AC power.
See the
SRX 3400 Services Gateway Hardware Guide
for specifications.
3.
For each power supply:
a.
Insert the appliance coupler end of the power cord into the appliance inlet
on the power supply.
b.
Insert the power cord plug into an external AC power source receptacle.
NOTE:
Each power supply must be connected to a dedicated AC power feed and a
dedicated external circuit breaker. We recommend that you use a 15 A (250 VAC)
minimum, or as permitted by local code.
Step 5: Connect the Ground and Power Cables
■
15
Step 5: Connect the Ground and Power Cables