A DC-powered services gateway is equipped with a DC terminal block that is rated for
the power requirements of a maximally configured services gateway. To supply
sufficient power, terminate the DC input wiring on a facility DC source capable of
supplying at least 30 A @ -48 VDC for the system. We recommend that the 48 VDC
facility DC source be equipped with a circuit breaker rated at 40 A (-48 VDC) minimum,
or as required by local code. Incorporate an easily accessible disconnect device into
the facility wiring. In the United States and Canada, the -48 VDC facility should be
equipped with a circuit breaker rated a minimum of 125% of the power provisioned for
the input in accordance with the National Electrical Code in the US and the Canadian
Electrical Code in Canada. Be sure to connect the ground wire or conduit to a solid
office (earth) ground. A closed loop ring is recommended for terminating the ground
conductor at the ground stud.
•
Run two wires from the circuit breaker box to a source of 48 VDC. Use appropriate
gauge wire to handle up to 40 A.
•
A DC-powered services gateway that is equipped with a DC terminal block is intended
only for installation in a restricted access location. In the United States, a restricted
access area is one in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code ANSI/NFPA 70.
NOTE:
Primary overcurrent protection is provided by the building circuit
breaker. This breaker should protect against excess currents, short circuits,
and earth faults in accordance with NEC ANSI/NFPA70.
•
Ensure that the polarity of the DC input wiring is correct. Under certain conditions,
connections with reversed polarity might trip the primary circuit breaker or damage
the equipment.
•
For personal safety, connect the green and yellow wire to safety (earth) ground at both
the services gateway and the supply side of the DC wiring.
•
The marked input voltage of -48 VDC for a DC-powered services gateway is the nominal
voltage associated with the battery circuit, and any higher voltages are only to be
associated with float voltages for the charging function.
•
Because the services gateway is a positive ground system, you must connect the
positive lead to the terminal labeled
RETURN
, the negative lead to the terminal labeled
-48V
, and the earth ground to the chassis grounding points.
DC Power Disconnection Warning
WARNING:
Before performing any of the following procedures, ensure that
power is removed from the DC circuit. To ensure that all power is off, locate
the circuit breaker on the panel board that services the DC circuit, switch the
circuit breaker to the
OFF
position, and tape the switch handle of the circuit
breaker in the
OFF
position.
Copyright © 2017, Juniper Networks, Inc.
352
SRX5400 Services Gateway Hardware Guide
Summary of Contents for SRX5400
Page 12: ...Copyright 2017 Juniper Networks Inc xii SRX5400 Services Gateway Hardware Guide ...
Page 20: ...Copyright 2017 Juniper Networks Inc xx SRX5400 Services Gateway Hardware Guide ...
Page 26: ...Copyright 2017 Juniper Networks Inc xxvi SRX5400 Services Gateway Hardware Guide ...
Page 28: ...Copyright 2017 Juniper Networks Inc 2 SRX5400 Services Gateway Hardware Guide ...
Page 52: ...Copyright 2017 Juniper Networks Inc 26 SRX5400 Services Gateway Hardware Guide ...
Page 114: ...Copyright 2017 Juniper Networks Inc 88 SRX5400 Services Gateway Hardware Guide ...
Page 132: ...Copyright 2017 Juniper Networks Inc 106 SRX5400 Services Gateway Hardware Guide ...
Page 136: ...Copyright 2017 Juniper Networks Inc 110 SRX5400 Services Gateway Hardware Guide ...
Page 146: ...Copyright 2017 Juniper Networks Inc 120 SRX5400 Services Gateway Hardware Guide ...
Page 156: ...Copyright 2017 Juniper Networks Inc 130 SRX5400 Services Gateway Hardware Guide ...
Page 168: ...Copyright 2017 Juniper Networks Inc 142 SRX5400 Services Gateway Hardware Guide ...
Page 172: ...Copyright 2017 Juniper Networks Inc 146 SRX5400 Services Gateway Hardware Guide ...
Page 208: ...Copyright 2017 Juniper Networks Inc 182 SRX5400 Services Gateway Hardware Guide ...
Page 224: ...Copyright 2017 Juniper Networks Inc 198 SRX5400 Services Gateway Hardware Guide ...
Page 234: ...Copyright 2017 Juniper Networks Inc 208 SRX5400 Services Gateway Hardware Guide ...
Page 236: ...Copyright 2017 Juniper Networks Inc 210 SRX5400 Services Gateway Hardware Guide ...
Page 268: ...Copyright 2017 Juniper Networks Inc 242 SRX5400 Services Gateway Hardware Guide ...
Page 270: ...Copyright 2017 Juniper Networks Inc 244 SRX5400 Services Gateway Hardware Guide ...
Page 274: ...Copyright 2017 Juniper Networks Inc 248 SRX5400 Services Gateway Hardware Guide ...
Page 284: ...Copyright 2017 Juniper Networks Inc 258 SRX5400 Services Gateway Hardware Guide ...
Page 296: ...Copyright 2017 Juniper Networks Inc 270 SRX5400 Services Gateway Hardware Guide ...
Page 344: ...Copyright 2017 Juniper Networks Inc 318 SRX5400 Services Gateway Hardware Guide ...
Page 352: ...Copyright 2017 Juniper Networks Inc 326 SRX5400 Services Gateway Hardware Guide ...
Page 360: ...Copyright 2017 Juniper Networks Inc 334 SRX5400 Services Gateway Hardware Guide ...
Page 366: ...Copyright 2017 Juniper Networks Inc 340 SRX5400 Services Gateway Hardware Guide ...
Page 394: ...Copyright 2017 Juniper Networks Inc 368 SRX5400 Services Gateway Hardware Guide ...