9
www.juwent.com.pl
A minimal distance of the unit to the wall or ceiling necessary to ensure a free air supply
to the fan is: 18cm for TROPIC-1 units, 25cm for TROPIC-2 units
When it is necessary to hang the unit on a partition, e.g. made of steel sheets, stiffening
profiles should be used to avoid vibrations of the partition generated by the unit
operation and the noise level increase in the compartment.
A minimal distance of the heating unit to the construction partition from the unit sides
is about 20cm.
8. WATER INSTALLATION
It is recommended:
»
- to connect the unit to the heating network by means of the lower spout of the heater and
the return of the heating medium by means of the top spout;
»
- to use cut-off valves upstream and downstream the unit to enable its dismounting without
the necessity to drain the supply installation.
The solenoid valves should be connected in the heating medium supply line from the unit.
The venting and draining of the heaters of the units is foreseen centrally in the network.
The vents and drain valves located in the installation outside the unit should be used.
The heaters of the units in the ceiling option mounting cannot be drained centrally.
The imprecise venting of the heater can be a reason for which the unit does not reach
planned parameters.
The weight of installation pipes should not rest on the spouts of the heater.
When connecting the heater to the heating network the spouts of the heater should be protected
against breaking in a way presented in the picture.
The heater damages arisen for the afore-mentioned reason are not covered by the
warranty.