KNX/EIB
Switch Actuator with Secure
5
Product
Load type
Rated power
Life cycles
ARSA-xx/20.S
Incandescent lamp
5000W
>30000
xx=04/08/12
Halogen lamp
4000W
>5000
Standard/Electronic ballast
4000W
>6000
Fluorescent lamp
(
uncompensated
)
4000W
>5000
Fluorescent lamp
(
parallel compensated
)
2800W
>5000
Motor
3675W
>30000
LED (Inrush current470A/210us)
800W
>50000
Note: The above load is only for single lamps. In the case of several lamps in parallel, the load will
be reduced, although the power is unchanged, but the instantaneous impact of current will increase,
and easy to make the relay contacts melted. In normal use, the maximum output current is preferably
less than 16A for resistive load, and inductive load and capacitive load will be lower.
Application program
Max. number of
communication objects
Max. number of
group addresses
Max. number
of associations
Secure group
addresses
Switch Actuator with Secure,
4-Fold/3.0
86
500
500
130
Switch Actuator with Secure,
8-Fold/3.0
168
500
500
260
Switch Actuator with Secure,
12-Fold/3.0
246
500
500
390