KNX/EIB
Switch Actuator with Secure
51
5.2.2. Time function object of “Switch actuator”
Fig. 5.2.2 “Switch Actuator” timing communication object for every output
No.
Function
Object name
Data type Flags
DPT
6
Output of staircase lighting
Output A-{{...}} 1bit
C,W
1.001 switch
It is used to switch on the staircase lighting by this object, which will be enabled when selecting
“Staircase lighting” in the parameter “The mode of time function”.
6
Switch out with delay
Output A-{{...}} 1bit
C,W
1.001 switch
It is used to switch on the time delay by this object, which will be enabled when selecting “Delay
switch” in the parameter “The mode of time function”.
6
Switch out with flashing
Output A-{{...}} 1bit
C,W
1.001 switch
It is used to switch on the flash output by this object, which will be enabled when selecting
“Flashing switch” in the parameter “The mode of time function”.
7
Switch time function
Output A-{{...}} 1bit
C,W
1.003 enable
This object will be started when enabling the time function which can be enabled by this object. It
will enable the timing function when receiving the value “1”; time function will disable it when receiving
“0”. After the time function is disabled,the current delay time counter will be cleared,and the delaying
operation will be ignored,apply to delay switch/flash switch/staircase lighting.
Enable is a default setting for the time function after bus voltage recovery.
8
Warning of staircase
Output A-{{...}} 1bit
C,T
1.005 alarm
It will be enable while selecting warning by this object in the parameter “Warning mode for ending
of staircase”. It will send “1” to the bus when the alarm is starting.
9
Duration of staircase
Output A-{{...}} 2byte
C,W,R
7.005 time (s)
This object will be enabled when selecting “enable” in the parameter “Modify the duration via
object (0...60059 seconds)” to modify the duration of the staircase lighting.
Table 5.2.2 Timing function communication table