KNX/EIB
KNX Gateway for IR
7
Chapter 4
Project design and Application
General Setting
General setting includes device In operation setting and channel function setting. In operation
setting is used for indicating whether the device application layer running normally. Channel function
can be configured Universal IR control or Air-condition control, up to set 2 channels. But only one of the
channels is supported to Air-condition control. That is when Channel 1 is used for Air-condition control,
and Channel 2 is only used for Universal IR control; if Channel 1 is used for Universal IR control, and
Channel 2 can be used for Air-condition control.
Universal IR control
Each channel up to support 30 IR code configurations is used for universal control, such as Fan, TV,
DVD and etc. You can set the object datatype 1bit or 1byte, the object value, the corresponding IR code,
and the status feedback to trigger the IR code to emit. Each IR code can set emission time and sending
count.
In addition, KNX Gateway for IR,Flush mounted also supports whether to connect with current
detection status, and you can decide whether to emit IR code according to the current switch status
after connecting.
Application
Max.number of
communication
objects
Max. Number of
group address
Max. number of
associations
KNX Gateway for IR,Flush mounted,2-Fold/1.0
KNX Gateway for IR,Ceiling/1.0
167
500
500