KNX/EIB
KNX Gateway for IR
26
5.5 Parameter window “Current detect setting”
Note: Only the Flush mounted supports current detection function, and the Ceiling not displays
this window.
Fig.5.5 “Current detect setting” parameter window
Internal current detect setting
Parameter “Object datatype of current detection”
This parameter is for setting the object datatype of current detection value. Options:
Value in mA(DPT 7.012)
Float Value in mA(DPT 9.021)
Value in mA(DPT 7.012): the unit of output current value is mA, integer data.
Float Value in mA(DPT 9.021): the unit of output current value is mA, float data.
Parameter “Send current value”
This parameter is for setting whether to send current detection value, or setting the sending
conditions. Current value is sent to the bus by the object “Current value(mA)”. Options:
No send
Send on change
Send cyclically
Send on read only