KNX/EIB
KNX Gateway for IR
31
86
Current temperature setpoint
CH1-{{AC}}: Status
1byte
2byte
C,R,T
5.010 counter pulses
9.001 temperature
This communication object is used to feedback actual setpoint temperature value of Air-condition to
the bus.
Object datatype is set by parameter.
87
Control mode
CH1-{{AC}}: Status
1byte
C,R,T
20.105 HVAC control mode
This communication object is used to send the control telegram of each mode of Air-condition to
bus.
88
Fan speed
CH1-{{AC}}: Status
1byte
C,R,T
5.010 counter pulses
9.001 temperature
The communication object is used to feedback current fan speed status of Air-condition to bus.
89
Wind swing=1/stop=0
CH1-{{AC}}: Status
1bit
C,R,T
1.017 trigger
The communication object is used to feedback wind swing status of Air-condition to bus.
Telegram value: 0——stop/1——swing
Table 6.2 “Air-condition control” communication object
6.4 “Sequence mode” communication object
Fig.6.4 “Sequence mode”
通讯对象
NO. Object Function
Name
Data
Type
Flag
DPT
2
Sequence trigger value
{{Sequence 1}}
1bit
1byte
C,W,U
1.001 switch
17.001 scene number
This communication object is used to receive the sequence trigger value from bus. Object
datatype is set by parameter.
The name in parentheses{{}} changes with the parameter “Description (max 30 char.)”. If
description is empty, display “Sequence x” by default.
Table 6.4 “Sequence mode” communication object