KNX/EIB
KNX Gateway for IR
32
6.5 “Current detect” communication object
Fig.6.5 “Current detect” communication object
NO. Object Function
Name
Data
Type
Flag
DPT
162
Switch ON/OFF
Current detection
1bit
C,R,T
1.001 switch
This communication object is used to send switch status of the device current detection to bus.
163
Current value(mA)
Current detection
2byte
C,R,T
7.012 current (mA)
9.021 current (mA)
This communication object is used to send current value of detection to bus. Object datatype is
set by parameter.
164
CH1-External switch ON/OFF
Current detection
1bit
C,W,U
1.001 switch
This communication object is visible when channel 1 is connected with external current detection.
Used to receive the current status that the current detection device detects from bus (On/Off).
165
CH1-External error report
Current detection
1bit
C,R,T
1.005 alarm
This communication object is used to send external current detection error telegram of channel 1.
166
CH2-External switch ON/OFF
Current detection
1bit
C,W,U
1.001 switch
This communication object is visible when channel 1 is connected with external current detection.
Used to receive the current status that the current detection device detects from bus (On/Off).
167
CH2-External switch ON/OFF
Current detection
1bit
C,R,T
1.005 alarm
This communication object is used to send external current detection error report of channel 2.
Table 6.5 “Current detect” communication object