19
This parameter defines whether scene x control function is active. Options:
Active
Inactive
If selecting ―active‖, the following parameters will be visible.
—
Parameter “Name of scene x”
This parameter is used to set the name that is shown in the TFT operation system for scene x, at
most 10 characters can be input here.
—
Parameter “Icon number of scene x”
This parameter is used to set the icon number that is shown in the TFT operation system for
scene x. Option: 0…63
Currently workable icon number is 0…23, other is reserved.
—
Parameter “Number of scene ”
The parameter is used to set an arbitrary scene number from 1 to 64 which can be sent out via
the object ―number of scene‖ for an operation of the TFT. Options: 1…64
—
Parameter “Storage function scenes”
It is used to set whether the scene storage function is enabled. Options:
Inactive
Active
With the setting ―Active‖, the following parameter ―Duration of long operation=entry*0.1s‖
will be visible. The object ―Number of scene‖ can send a telegram of storage scene via a long
operation.
—
Parameter “Duration of long operation=entry*0.1s”
This parameter will be visible if the option ―active‖ is selected with the parameter ―storage
function scenes‖. It is used to define the time which a long operation is recognized. Option: 3…100
5.5. Parameter window “HVAC”
Parameter window ―HVAC‖ can be shown in fig.5.5. The application is mainly used for control
room temperature controller, make it turn on or off automatically, and in the case of someone or no
one can also make it regulate the indoor temperature automatically according to predefined
procedure to a comfortable temperature. Control type: 1bit (on/off), 1byte (continuous), fan coil.