23
setpoint for operating modes. Options:
Relative
Absolute
If selecting relative setpoint, mean that a comfort temperature (base setpoint) is defined and
other setpoints such as temperature at standby or night refer to this point. For example, the standby
temperature 2
℃
is set lower than the comfort temperature (base setpoint). At a comfort temperature
of 21
℃
, the standby temperature is 19
℃
. If you raise the comfort temperature to 22
℃
, the standby
temperature automatically changes to 20
℃
. If the standby temperature is raised from 20
℃
to 21
℃
via operating the TFT or other ways, then when the comfort temperature is raised from 22
℃
to 23
℃
again, and the standby temperature will also raise to 22
℃
automatically.
If selecting absolute setpoint, the setting allows you to choose a separate temperature on the
room temperature controller for each setpoint; the room temperature controller always refers to this
setting in the respective operating mode. For example, the standby temperature is set permanently
at 19
℃
, if you raise the comfort temperature from 21
℃
to 22
℃
, the standby temperature does not
change.
—
Parameter “Base setpoint heating”/ Parameter “Base setpoint Cooling (Celsius) ”
This parameter specifies the comfort temperature (base setpoint) for the heating/cooling mode.
Options: 10…40
—
Parameter “Setpoint decrease for standby mode, heating (Celsius) ” / Parameter
“Setpoint standby Cooling, incremental (Celsius)”
These parameters are only visible if the option ―relative‖ is selected with the parameter
―setpoint temperatures for operating modes‖. The standby setpoint allows you to specify the number
of degrees Celsius that the base setpoint is raised or lowered during standby mode for the
heating/cooling. For example, here set 3
℃
for the standby heating setpoint, if he base setpoint is
23
℃
, the standby setpoint will be 20
℃
. If here set 3
℃
for the standby cooling setpoint, if he base
setpoint is 23
℃
, the standby setpoint will be 26
℃
. Option: 0…15
—
Parameter “Setpoint decrease for night mode, heating (Celsius) ” / Parameter
“Setpoint night Cooling, incremental (Celsius)”
These parameters are only visible if the option ―relative‖ is selected with the parameter
―setpoint temperatures for operating modes‖. The night setpoint allows you to specify the number of
degrees Celsius that the base setpoint is raised or lowered during night mode for the heating/cooling.
For example, here set 3
℃
for the night heating setpoint, if he base setpoint is 23
℃
, the night
setpoint will be 20
℃
. If here set 3
℃
for the standby cooling setpoint, if he base setpoint is 23
℃
, the
night setpoint will be 26
℃
. Option: 0…15
—
Parameter “Setpoint standby heating, absolute (Celsius) ” / Parameter “Setpoint
standby cooling, absolute (Celsius)”
These parameters are only visible if the option ―absolute‖ is selected with the parameter
―setpoint temperatures for operating modes‖, which are used to specify the individual standby