                                  FIRE DAMPERS / SHUTTER TYPE 

K-VENTIL ventilation equipment 

                                                  export@kventil.com | +356 79667970 | www.kventil.com

 

 
FD/DFD-10 DESIGN & CONSTRUCTION FEATURES  
 
Description 
 

Model FD/DFD-10 is a fire damper approved for installation in walls with a fire resistance 
rating of less than 3 hours. This damper installed vertically in HVAC systems that 
automatically shut down in the event of fire. 
 

Construction 
 

Frame : Roll formed, galvanized steel  
Blades : Low profile roll formed, galvanized steel 
 
 
 

Features 

 

Stainless steel closure springs        
Fusible links [165

º

F (74

º

C) standard] 

Vertical Mount 
 

   

        

                                       

      

Dynamic Curtain Fire Damper                                          Static Curtain Fire Damper 

 
 
Optional Features 

 
Sealed transitions and sleeves 
One piece retaining angle (POC) 
Transitions (A,B,C & CR ) 

 

Summary of Contents for FD-10

Page 1: ...FIRE DAMPERS SHUTTERTYPE K VENTIL ventilation equipment export kventil com 356 79667970 www kventil com...

Page 2: ...ess than 3 hours This damper installed vertically in HVAC systems that automatically shut down in the event of fire Construction Frame Roll formed galvanized steel Blades Low profile roll formed galva...

Page 3: ...vens are galvanized steel and are available in 1 0mm 1 5mm thicknesses and lengths up to 914mm C dimension specifies location of damper within the sleeven Minimum is 102mm Maximum is L less 102mm whic...

Page 4: ...FIRE DAMPERS SHUTTERTYPE K VENTIL ventilation equipment export kventil com 356 79667970 www kventil com FD DFD 10 TRANSITIONS AND SIZE LIMITATIONS Transition Details...

Page 5: ...inimum sleeve gauges Maximum sleeve thickness is 10 gauge 3 5mm Sleeve inside dimensions must equal damper out side dimensions Sleeves shall extend a maximum of 6in 152mm beyond the wall opening on ea...

Page 6: ...mm steel pop rivets Securing Fire Damper and Sleeves to Wall Openings The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall Fire damper and slee...

Page 7: ...ucts to Fire Damper Sleeves Any duct connection other than breakaway is considered rigid The connections shown are considered breakaway Factory furnished duct collars on type R and CR fire dampers are...

Page 8: ...ORDER PARAMETERS FD 10 F00 01 L1200 N 1000X700 FD 10 Static Fire Damper 74 C Fusible links N Neck Size DFD 10 Dynamic Fire Damper 74 C Fusible links D Neck Diameter L Requested Product Length F00 No F...