Appendix A - Electrified Cylindrical Lock Wiring
Instructions
Wiring Instructions for 9K Series
Electrified Cylindrical Locks with Request-to-exit
Wiring diagram
The diagram below shows how to wire
9K electrified locks
Power Supply
24 Volts AC or DC
Ceiling
*Note:
In some door applications (for example, fire
doors), it may not be possible to make extra holes into
the door. In such scenarios, the TCM may be installed in
a secure location at no more than 20 feet from the door.
Electrified cylindrical chassis—
9KW shown with RQE.
Run wires through the door or
mount wires to the door surface
with wire molding. To find the
correct wire guage for wire runs,
see Figure A2 on the next page.
TCM
(Temperature
Control Module)
Insert TCM into the
1" dia. extension.*
(1" dia. x 3" deep
hole).
8WDTL
Door transfer loop
Figure A1: Wiring diagram for 8KW and 9KW electrified locks (9KW with RQE shown)
Unit
Voltage
Current
8KW (RQE not
available
24 volts AC or DC
0.18 amp continuous
duty
9KW with and
without RQE
24 volts AC or DC
0.18 amp continuous
duty
Electrical requirements
The following table describes the voltage and current specifications for the 8KW
and 9KW locks, with RQE (REX) switch, and door monitoring switch.