Mounting and installation
User Manual B-Net 93 60
22
© Kaba Benzing GmbH
01/2006
5.3.4 Door
control
Line to door-opener, door-frame contact, door-opener push button, door handle
contact, etc.
Line requirements
Cables with a cable diameter from 0.5 mm to 0.8 mm can be used.
Recommended cable
CAT.5 S-UTP 4 x 2 AWG 24 or AWG 22 (according to EIA/TIA568) or higher.
5.3.5 Host
connection
Ethernet
Connecting cable from terminal to the Ethernet’s RJ45 connector.
Line requirements
Connection takes place via 1:1 patch cable.
Analog modem
Connecting cable from terminal to TAE outlet.
Recommended cable
Data cable with TAE jack 3 m long, item no. 04106703.
ISDN modem
Connecting cable from terminal to RJ45 outlet.
Recommended cable
Telephone cable with RJ45 jack 3 m long, item no. 04106702.
Partyline
What must be considered?
The complete bus connection (master lines and branch lines) may be up to 2,000
meters long. One branch line may not exceed 100 m.
A maximum of 30 devices may be operated with one partyline.
The length of the master line or the branch line can be increased with repeaters.
Please keep in mind that the connecting line of a repeater may not exceed
1,500 m. Up to 3 repeaters may be cascaded in an extension of a bus connection.
Line requirements
Shielded line with twisted wire pairs,
for instance standard telephone cable J-Y (St) Y 4 x 2 x 0.6 mm.
Recommended cable
CAT.5 S-UTP 4 x 2 x AWG 24 or AWG 22 (nach EIA/TIA 568), or higher (CAT.6,
CAT.7).