blueplanet
110 TL3 US
125 TL3
AC Output levels
Output levels (AC)
Nominal power
110 kVA
125 kVA
Nominal voltage
480 V (3P+PE)
Voltage range: continuous operation
300 V - 552 V
Nominal current
3 x 132.3 A
3 x 150.5 A
Max. continuous current
3 x 132.3 A
3 x 152 A
Contribution to peak short-circuit cur-
rent ip
193 A
260.8 A
Initial short-circuit alternating current
(lk” first single-period effective value)
137 A
150.8 A
Short circuit current continuous [ms]
(max output fault current)
134 A
150 A
Inrush current
5 A [RMS (20ms)]
Nominal frequency
50/60 Hz
Frequency range
45 - 65 Hz
Reactive power
0-100 % Snom
cos phi
0.3 - 1 ind/cap
Number of feed-in phases
3
Distortion factor (THD)
< 3 %
Max. voltage range (up to 100 s)
600 V
AC overvoltage protection
Base
blueplanet
110 TL3 US
125 TL3 US
Max. efficiency
99.1 %
98.98 %
European efficiency
98.8 %
98.73 %
CEC efficiency
98.8 %
98.70 %
Self consumption: Standby
< 10 W
Infeed from
> 200 W
Protection class / over voltage category
I / III (AC) II (DC)
Transformer
no
Grid monitoring
Country-specific
Distribution system
TN-C system, TT system, Solid grounded wye
4.2
General data
General data
Display
LEDs
Control elements / operating control
Web server
Menu language
EN; DE; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO
Interfaces
2 x Ethernet, USB, 2x RS485 (1x reserved for string combiner com.), optional
Fault signal relay
yes (integrated switch)
DC switch / AC switch
no / yes (XL version) / no
Cooling
temp. regulated fan, max air throughput 364 m³/h
Number of fans
3x outside, 1x inside
Noise emission
<60 db(A)
Housing material
AL
H x W x D
28,30 inch x 28,30 inch x 18,11 inch
Weight
172 Ib
Grid connection directive
Overview: see homepage, download area
Manual
Technical data | 4
KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Page 13
EN-US