NOTE: Please do not under any circumstances connect the Ethernet cable to the unshielded RJ45 slot
marked J200 as this typically causes damage to the printed circuit board!
1. Use a functioning Ethernet slot on the external network end.
2. It may be necessary to take additional IT configuration measures in the external network so that the device is as-
signed an IP address.
3. Next, launch the browser on the terminal device and enter the IP address of the device:
ð
http://<IP address of the device>
ð
The IP address can either be requested from the network administrator or determined using an IP scanner tool.
4. There is also the option of addressing the device using its host name. In its factory default state, the host name con-
sists of a combination of the device derivative designation and the serial number, as shown below:
<Device designation serial number>, for example:
↻
or
8
F
If this is unsuccessful, please use the full domain name:
http://bp125-125TL01234567<ExternalNetworkDomainName> or http://bp87-87-0TL01234567<ExternalNetworkDo-
mainName>
8.4.5
Starting up a plant segment
The following figure provides an example of the structure of a plant segment consisting of a Segment Controller
and a certain number of KACO devices with string combiner (SC) combinations.
M
O
D
-
B
U
S
R
TU
R
S4
8
5
D
C
D
C
M
O
D
-
B
U
S
R
TU
R
S4
8
5
M
O
D
-
B
U
S
R
TU
R
S4
8
5
D
C
ARGUS
SC
BP125
ARGUS
SC
BP125
Ethernet
ARGUS
SC
BP125
Ethernet
Ethernet
Up to 45
Segment Controller *)
Ethernet
Notebook
*): MC blue‘Log
Inverter
Inverter
Inverter
Fig. 46:
Start-up via Segment Controller
Area of application
The network infrastructure already exists. All of the KACO devices in the segment can be reached via Ethernet
using a Segment Controller.
NOTE: When multiple Segment Controllers are present, keep in mind that the Segment Con-
trollers must not be connected to one another via the network during start-up.
9
Once start-up is complete (assignment of devices to the individual Segment Controllers), these can be con-
nected to the network by pressing a
Main network switch
.
8
If the device serial number features a “.” dot, then this “.” dot is replaced with a “-” dash in the host name as,
according to RFC229, host names must not contain any “.” dots.