4
1
2
3
4
Maximum apparent
power Slim
1000 – S
max
[VA]
NOTE: The max. apparent power limits the internal power of the
device.
More detailed information at:
Other grid-supporting functions that are effective in the case of active
power [See section 10.4
F
Enter the value or set the value using the slider.
The apparent power is limited globally to the configured value in VA. All
active and reactive power control values use S
lim
instead of S
max
as
100 %, if S
lim
is configured.
4
1
2
3
4
Maximum active power
Plim
1.0 - 100.0 [% Slim]
Password protection
Status
More detailed information at:
Other grid-supporting functions that are effective in the case of active
power [See section 10.4
F
Enter the value or set the value using the slider.
Active power is limited globally to the configured value in % S
lim
or S
max
.
1 Optional: Activate password protection.
2 Confirm the action field.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
EPC (extended power
control)
NOTE: EPC settings
Fallback power
0 – 1000 %
Timeout
3 – 100000 s
1 Set fallback power.
2 Set time until shutdown takes place.
3 Apply the values using the Apply button.
4
1
2
3
4
Power rampup active
NOTE: Power ramp-up is used to ramp up the power gradually
Power rampup gradi-
ent
1 – 600 [% / min]
F
Set increase.
Rampup on every con-
nect
Status
Rampup on first con-
nect
Status
Rampup after grid fail-
ure
Status
Password Protection
Status
1 Activate option.
2 Activate optional password protection.
3 Confirm action field
4
1
2
3
4
Priority mode
Q-Priority | P-Prior-
ity
F
Set priority for reactive power – Q or active power – P.
NOTE: When it comes to P priority, the reactive power adjustment
range is limited subject to the active power that is currently available
and fed in.
Kaco blueplanet 29.0TL3
Page 51
EN