No. Grid
LED
LED
Display
Status description
Action
Pers
.
58
Control board overtemp.
The temperature inside the device was too
high. The device shuts down to avoid hard-
ware damage.
Ensure sufficient
ventilation.
E
59
Self test error
A fault occurred during a self-test.
Notify your author-
ized electrician!
E
67
Fault at power section 1
There is a fault in the power section.
Notify your author-
ised electrician!
E
70
Fault in fan 1
The fan is malfunctioning.
Replace defective
fan See Mainten-
ance and
troubleshooting
chapter.
E
74
External idle power require-
ment
The grid operator limits the feed-in power of
the device via the transmitted reactive power
factor.
-
-
81
Protection shutdown line
volt. L1
Overvoltage has been detected on a con-
ductor. An internal protective mechanism has
disconnected the device to protect it against
damage.
In case of repeated
occurrence: Notify
your authorized
electrician!
E
82
Protection shutdown line
volt. L2
Overvoltage has been detected on a con-
ductor. An internal protective mechanism has
disconnected the device to protect it against
damage.
In case of repeated
occurrence: Notify
your authorized
electrician!
E
83
Protection shutdown line
volt. L3
Overvoltage has been detected on a con-
ductor. An internal protective mechanism has
disconnected the device to protect it against
damage.
In case of repeated
occurrence: Notify
your authorized
electrician!
E
84
Protection shutdown under-
volt. DC link
A voltage deviation has been found in the DC
link. An internal protective mechanism has dis-
connected the device to protect it against
damage. In a TN-C-S grid, the PE must be con-
nected to the device and at the same time the
PEN bridge in the device must be removed.
In case of repeated
occurrence: Notify
your authorized
electrician!
E
85
Protect. shutdown overvolt.
DC link
A voltage deviation has been found in the DC
link. An internal protective mechanism has dis-
connected the device to protect it against
damage. In a TN-C-S grid, the PE must be con-
nected to the device and at the same time the
PEN bridge in the device must be removed.
In case of repeated
occurrence: Notify
your authorized
electrician!
E
86
Protect. shutdown DC link
asymmetry
Overvoltage has been found in the DC link. An
internal protective mechanism has disconnec-
ted the device to protect it against damage.
In case of repeated
occurrence: Notify
your authorized
electrician!
E
87
Protect. shutdown overcur-
rent L1
A current that has been found on a conductor
is too high. An internal protective mechanism
has disconnected the device to protect it
against damage.
In case of repeated
occurrence: Notify
your authorized
electrician!
E
88
Protect. shutdown overcur-
rent L2
A current that has been found on a conductor
is too high. An internal protective mechanism
has disconnected the device to protect it
against damage.
In case of repeated
occurrence: Notify
your authorized
electrician!
E