Kaden Installation Manual |
23
Outdoor unit wiring
WARNING
Before performing any electrical or wiring work, turn off the
main power to the system.
Electrical requirement
The indoor unit is powered by the outdoor unit. Do not power
indoor unit from separate power source.
WARNING
Standards for electrical wiring and equipment differs in
each country or region. Before you start electrical working,
confirm related regulations, codes or standards.
Cable
Conductor
size (mm²)
Type
Remarks
Power
cable
2.5
Type
60245
IEC 57
2 core + Earth
(Ground)
1 Ø 230 V
Cable
Conductor
size (mm²)
Type
Remarks
Interconnect
power cable
1.5
Type
60245
IEC 57
2 core + Earth
(Ground)
1 Ø 230 V
Cable
Conductor
size (mm²)
Type
Remarks
Signal
cable
1.0
Type
60245
IEC 57
2 core Shielded
Cable length: Limit voltage drop to less than 2%.
Increase cable gauge if voltage drop is 2% or more.
If the interconnect cable exceeds 30M in length 2.5mm thick
cable should be used.
The cable specifications are based on the assumption that a
metal or plastic conduit is used with no more than three cables
contained in a conduit and a voltage drop of 2%.
Preparing cable
1.
Selecting cable
Select the power source cable and connecting cable in
accordance with the specifications mentioned below:
a. Power source cable
3-core* 2.5mm² or more, conformed with 60245 IEC57.
When selecting the power source cable length, make sure
that voltage drop is less than 2%. If the voltage drop is
more than 2%, increase cable thickness.
b. Connecting cable
3-core* 1.5mm², conformed with 60245 IEC57.
2. Arrange each wire length as shown. Make sure that each
wire is stripped 10mm from the end.
3. Attach round crimp-type terminal to each wire as shown.
Select the size of round crimp-type terminal after
considering the specifications of terminal block and
wire diameter.
Wire end
10mm
Round crimp type
terminal
Sleeve
Signal cable
30mm or more
40mm or more
Power and interconnect cable
30mm or more
Earth wire
40mm or more