4. Indoor unit installation
Installation instructions – Indoor unit
NOTE:
Panel installation should be performed after piping and wiring have been completed.
Step 1: Select installation location
Before installing the indoor unit, you must choose an appropriate location. The following are standards that will help you choose an
appropriate location for the unit.
Proper installation locations meet the following standards:
✓
Enough room exists for installation and maintenance.
✓
Enough room exists for the connecting pipe and drainpipe.
✓
The ceiling is horizontal and its structure can sustain the
weight of the indoor unit.
✓
The air inlet and outlet are not blocked.
✓
The airflow can fill the entire room.
✓
There is no direct radiation from heaters.
DO NOT install unit in the following locations:
✕
Areas with oil drilling or fracking
✕
Coastal areas with high salt content in the air
✕
Areas with caustic gases in the air, such as hot springs
✕
Areas that experience power fluctuations, such as factories
✕
Enclosed spaces, such as cabinets
✕
Kitchens that use natural gas
✕
Areas with strong electromagnetic waves
✕
Areas that store flammable materials or gas
✕
Rooms with high humidity, such as bathrooms
or laundry rooms
Recommended distances between the indoor unit and the ceiling
The distance between the mounted indoor unit and the internal ceiling should meet the following specifications.
Distance from ceiling relative to height of indoor unit
Type
Model
A (mm)
H (mm)
B (mm)
KCS
KCS24
205
> 235
880
KCS36
245
> 275
KCS42
205
> 235
KCS48
245
> 275
Ceiling
Ceiling board
>2.5m
Front panel
Ground
A
B
(Ceiling hole)