background image

Phase Alarms

 – HD on Voltage (enable)

In case  the failure of any harmonics between 3...31 in the phase voltage exceeds the set value 

during the activation of alert, device warns the user. 

In this case;

- You should install harmonic filter to protect your devices.

Phase Alarms

 – THD on Current  (enable)

In case total harmonic failure in the phase of system exceeds the set value during the activation of 

alert, device warns the user. 

In this case;

- You should install harmonic filter to protect your devices.

Phase Alarms

 – HD on Current  (enable)

In case  the failure of any harmonics between 3...31 in the phase voltage exceeds the set value 

during the activation of alert, device warns the user. 

In this case;

- You should install harmonic filter to protect your devices.

1 9 1 1 8

1 9 1 1 9

1 9 1 1 10

1 9 1 2 1

General Alarms

 – 1. connector failure (K1...K6)    (enable)

In case of this alarm;

- (C1) common phase input may not be connected. 

- The fuse of (C1) common phase input may blowed out.

- Compensation connection may be made prior to current transformers.

- Removing the failure, steps internalized zero should be internalized again.

1 9 1 2 2

General Alarms

 – 2. connector failure (K7...K12)   (enable)

In case of this alarm;

- (C2) common phase input may not be connected. 

- The fuse of (C2) common phase input may blowed out.

- Compensation connection may be made prior to current transformers.

- Removing the failure, steps internalized zero should be internalized again.

1 9 1 2 4

General Alarms

 – Total Over Compensation (enable)

In case of this alarm ;

- The system may be kept in penalty.

- Review the capacitor power distribution in the steps.

- Please allow less powerful capacitors which can reach buffer values.

1 9 1 2 5

General Alarms

 – Total Under Compensation  (enable)

In case of this alarm ;

- The system may be kept in penalty.

- Review the capacitor power selection in the steps.

- Please insert the capacitors which the phase or the phases need.

1 9 1 2 6

General Alarms

 – System Error  (enable)

In case of this alarm;

- (C1,C2) common phase inputs may not be connected. 

- The fuse of (C1,C2) common phase inputs may blowed out.

- The fuses in the power line of capacitors may blowed out.

- Removing the failure, steps internalized zero should be internalized again.

1 9 1 2 7

General Alarms

 – Over Temperature (enable)

In case of this alarm;

- The temperature in the board exceeds the value setted.

- Please empower the panel cooling.

-“Temperature protection enable” may be preferred in the step protection function 

(Chapter 179641)

1 9 1 2

General Alarms

1 9 1 2 9

General Alarms

 – Step Change   (enable)

In case of this alarm;

- The old capacitor may be replaced with the new one, but power value is not entered, or the 

power of capacitor may be decreased 50%. 

1 9 1 2 10

General Alarms

 – Step Zero  (enable)

In case of this alarm;

- The fuses in the power line of capacitors may blowed out or contactor may be damaged.

- Removing the failure, steps internalized zero should be internalized again.

Summary of Contents for VARko-112-PC-TFT

Page 1: ...VARko 112 PC TFT Reactive Power Control Relay Banks Markets Oil Stations Schools Workshops Hotels 12 Steps KAEL M hendislik Elektronik Tic ve San Ltd ti www kael com tr RS485 MODBUS RTU...

Page 2: ...em is used in the micro processor Password protected Measuring temperature Following electrical parameters of three phases at the same time RS485 MODBUS RTU Voltage of phase V L N Current of phase I C...

Page 3: ...t use the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not interfere to...

Page 4: ...always located on the top of the screen 8 LCD screen is used in VARko 112 PC TFT to provide it to be more easier in use and be intelligible In case the keys are not pressed for a long time the device...

Page 5: ...n mode In this case it is required to draw enough current from each phase If enough current can not be drawn from any phase the device warns as current flow direction not detected and shows the phase...

Page 6: ...K10 K11 K12 N L1 I1 k1 Voltage inputs Current Transformer Inputs Load Fuse compatible to the capacitor power ALR ALR Alarm output FAN Fan output FAN 2A 2A VARko 112 PC TFT 230V AC X 5A Main Screen Tem...

Page 7: ...ll the values are entered in the same way by using up and down keys Press Apply key inorder to take the period of step activating into memory Save changes message will appear on the screen When Okay k...

Page 8: ...e entered The device directs the user with subcommand display continuously It is moved on the step of which the power is required to be entered by using the up and down keys In the meantime that line...

Page 9: ...s given and device warns the user In this case capacitors and devices in the system may be damaged or may not be operated properly Voltage protection activated may be preferred in the step protection...

Page 10: ...emoving the failure steps internalized zero should be internalized again 1 9 1 2 4 General Alarms Total Over Compensation enable In case of this alarm The system may be kept in penalty Review the capa...

Page 11: ...ill appear on the screen Pressing Okay key the value is taken into the memory 180 Save changes In case voltage protection is activated in the step protection function Chapter 19112 all steps are de ac...

Page 12: ...harmonic protection is activated in the step protection function Chapter 19118 all steps are de activated one by one to protect the capacitors when HDV setup value is exceeded 1 9 2 6 THD Current Set...

Page 13: ...utomatically and de activates the steps one by one 1 9 4 1 This is the section in which the temperature protection function is activated or de activated The over temperature alarm should also be activ...

Page 14: ...10 9 PASSWORD Re Enter New Password 0 Okay Save Password This is the section in which password is changed First old password must be entered correctly Number value of the digit under which blue line...

Page 15: ...emory Save changes message will appear on the screen Pressing Okay key the value is taken into the memory P S The security increases when giving different passwords for writing and reading data 1 11 5...

Page 16: ...oltage Protection disable Level Protection Function Harmonic Protection disable Password Procedure Password Settings disable Password Procedure Default Password 0000 refer to PS1 MODBUS RTU Setup Data...

Page 17: ...ity no even odd Device No 1 255 Device Protection Class IP 20 Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Connection Type On the front cover of...