THD Voltage Setting (% 1 – 100)
Apply
▲ +
▼ -
◄
008
Cancel
Okay
Exit
Voltage THD Alarm Setting
THDV
%
This is the section in which total harmonic distortion value (THDV) are entered for voltage. You
may enter a value between 1% and 100%. The value is setup to the required value by using the
up and down key starting from the digit where the blue line is. Then left key is pressed and the
blue underline moves next to the left digit. All values are entered in the same way by using up and
downkeys. “Select”
key is pressed to take them into the memory.
“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into
the memory.
007
Voltage THD Alarm Setting
THDV
%
Save
Changes ?
In case harmonic protection is
activated in the step protection
function (Chapter 19117), all
steps are de-activated one by
one to protect the capacitors
when THDV setup value is
exceeded.
1 9 2 5
HD Voltage Setting (% 1 – 100)
Apply
▲ +
▼ -
◄
006
Cancel
Okay
Exit
Voltage HD Alarm Setting
HDV
%
This is the section in which harmonic distortion value (HDV) are entered for voltage. You may
enter a value between 1% and 100%. The value is setup to the required value by using the up
and down key starting from the digit where the blue line is. Then left key is pressed and the blue
underline moves next to the left digit. All values are entered in the same way by using up and
downkeys. “Select”
key is pressed to take them into the memory.
“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into
the memory.
005
Voltage HD Alarm Setting
HDV
%
Save
Changes ?
In case harmonic protection is
activated in the step protection
function (Chapter 19118), all steps
are de-activated one by one to
protect the capacitors when HDV
setup value is exceeded.
1 9 2 6
THD Current Setting (% 1 – 100)
Apply
▲ +
▼ -
◄
020
Cancel
Okay
Exit
Current THD Alarm Setting
THDI
%
This is the section in which total harmonic distortion value (THDI) are entered for current. You
may enter a value between 1% and 100%. The value is setup to the required value by using the
up and down key starting from the digit where the blue line is. Then left key is pressed and the
blue underline moves next to the left digit. All values are entered in the same way by using up and
downkeys. “Select”
key is pressed to take them into the memory.
“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into
the memory.
020
Current THD Alarm Setting
THDI
%
Save
Changes ?
1 9 2 7
HD Current Setting (% 1 – 100)
Apply
▲ +
▼ -
◄
015
Cancel
Okay
Exit
Current HD Alarm Setting
HDI
%
This is the section in which harmonic distortion value (HDI) are entered for current. You may enter
a value between 1% and 100%. The value is setup to the required value by using the up and down
key starting from the digit where the blue line is. Then left key is pressed and the blue underline
moves next to the left digit. All values are entered in the same way by using up and downkeys.
“Select”
key is pressed to take them into the memory.
“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into
the memory.
015
Current HD Alarm Setting
HDI
%
Save
Changes
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8
1
3 4 5
7
9 10 11 12
2
6
8