THD Voltage Setting (% 1 – 100)

Apply

▲ +

▼ -

008

Cancel

Okay

Exit

Voltage THD Alarm Setting

  THDV

%

This is the section in which total harmonic distortion value (THDV) are entered for voltage. You 

may enter a value between 1% and 100%. The value is setup to the required value by using the 

up and down key starting from the digit where the blue line is. Then left key is pressed and the 

blue underline moves next to the left digit. All values are entered in the same way by using up and 

downkeys. “Select”

 

key is pressed to take them into the memory.

“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into 

the memory.

007

Voltage THD Alarm Setting

  THDV

%

Save

Changes ?

In case harmonic protection is 

activated in the step protection 

function (Chapter 19117), all 

steps are de-activated one by 

one to protect the capacitors 

when THDV setup value is 

exceeded. 

1 9 2 5

HD Voltage Setting (% 1 – 100)

Apply

▲ +

▼ -

006

Cancel

Okay

Exit

Voltage HD Alarm Setting

 HDV

%

This is the section in which harmonic distortion value (HDV) are entered for voltage. You may 

enter a value between 1% and 100%. The value is setup to the required value by using the up 

and down key starting from the digit where the blue line is. Then left key is pressed and the blue 

underline moves next to the left digit. All values are entered in the same way by using up and 

downkeys. “Select”

 

key is pressed to take them into the memory.

“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into 

the memory.

005

Voltage HD Alarm Setting

 HDV

%

Save

Changes ?

In case harmonic protection is 

activated in the step protection 

function (Chapter 19118), all steps 

are de-activated one by one to 

protect the capacitors when HDV 

setup value is exceeded.

1 9 2 6

THD Current Setting (% 1 – 100)

Apply

▲ +

▼ -

020

Cancel

Okay

Exit

Current THD Alarm Setting

  THDI

%

This is the section in which total harmonic distortion value (THDI) are entered for current. You 

may enter a value between 1% and 100%. The value is setup to the required value by using the 

up and down key starting from the digit where the blue line is. Then left key is pressed and the 

blue underline moves next to the left digit. All values are entered in the same way by using up and 

downkeys. “Select”

 

key is pressed to take them into the memory.

“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into 

the memory.

020

Current THD Alarm Setting

  THDI

%

Save

Changes ?

1 9 2 7

HD Current Setting (% 1 – 100)

Apply

▲ +

▼ -

015

Cancel

Okay

Exit

Current HD Alarm Setting

 HDI

%

This is the section in which harmonic distortion value (HDI) are entered for current. You may enter 

a value between 1% and 100%. The value is setup to the required value by using the up and down 

key starting from the digit where the blue line is. Then left key is pressed and the blue underline 

moves next to the left digit. All values are entered in the same way by using up and downkeys. 

“Select”

 

key is pressed to take them into the memory.

“Save changes?” message will appear on the screen. Pressing “Okay” key, the value is taken into 

the memory.

015

Current HD Alarm Setting

 HDI

%

Save

Changes

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

1

3 4 5

7

9 10 11 12

2

6

8

Summary of Contents for VARko-112-PC-TFT

Page 1: ...VARko 112 PC TFT Reactive Power Control Relay Banks Markets Oil Stations Schools Workshops Hotels 12 Steps KAEL M hendislik Elektronik Tic ve San Ltd ti www kael com tr RS485 MODBUS RTU...

Page 2: ...em is used in the micro processor Password protected Measuring temperature Following electrical parameters of three phases at the same time RS485 MODBUS RTU Voltage of phase V L N Current of phase I C...

Page 3: ...t use the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not interfere to...

Page 4: ...always located on the top of the screen 8 LCD screen is used in VARko 112 PC TFT to provide it to be more easier in use and be intelligible In case the keys are not pressed for a long time the device...

Page 5: ...n mode In this case it is required to draw enough current from each phase If enough current can not be drawn from any phase the device warns as current flow direction not detected and shows the phase...

Page 6: ...K10 K11 K12 N L1 I1 k1 Voltage inputs Current Transformer Inputs Load Fuse compatible to the capacitor power ALR ALR Alarm output FAN Fan output FAN 2A 2A VARko 112 PC TFT 230V AC X 5A Main Screen Tem...

Page 7: ...ll the values are entered in the same way by using up and down keys Press Apply key inorder to take the period of step activating into memory Save changes message will appear on the screen When Okay k...

Page 8: ...e entered The device directs the user with subcommand display continuously It is moved on the step of which the power is required to be entered by using the up and down keys In the meantime that line...

Page 9: ...s given and device warns the user In this case capacitors and devices in the system may be damaged or may not be operated properly Voltage protection activated may be preferred in the step protection...

Page 10: ...emoving the failure steps internalized zero should be internalized again 1 9 1 2 4 General Alarms Total Over Compensation enable In case of this alarm The system may be kept in penalty Review the capa...

Page 11: ...ill appear on the screen Pressing Okay key the value is taken into the memory 180 Save changes In case voltage protection is activated in the step protection function Chapter 19112 all steps are de ac...

Page 12: ...harmonic protection is activated in the step protection function Chapter 19118 all steps are de activated one by one to protect the capacitors when HDV setup value is exceeded 1 9 2 6 THD Current Set...

Page 13: ...utomatically and de activates the steps one by one 1 9 4 1 This is the section in which the temperature protection function is activated or de activated The over temperature alarm should also be activ...

Page 14: ...10 9 PASSWORD Re Enter New Password 0 Okay Save Password This is the section in which password is changed First old password must be entered correctly Number value of the digit under which blue line...

Page 15: ...emory Save changes message will appear on the screen Pressing Okay key the value is taken into the memory P S The security increases when giving different passwords for writing and reading data 1 11 5...

Page 16: ...oltage Protection disable Level Protection Function Harmonic Protection disable Password Procedure Password Settings disable Password Procedure Default Password 0000 refer to PS1 MODBUS RTU Setup Data...

Page 17: ...ity no even odd Device No 1 255 Device Protection Class IP 20 Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Connection Type On the front cover of...