4. Press «Enter».
The setting is applied.
5. Press «Down».
The
pB line is displayed.
6. If necessary, adjust the value for the
pB switching differential in the same manner.
Activating the remote control
➤ Activate remote control see chapter 8.2.13.
Result SIGMA CONTROL 2 remote control is activated.
Set the remote operating mode
Precondition The electrical connection is made.
Access level 2 is activated.
1. Open the 5.2.3
<Configuration – Pressure control – Load control> menu.
2. Use «Up» or «Down» to select the
Remote mode line.
3. Press «Enter».
The setting mode is active.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.2.3 Load control
Menu
Local mode:
pA/pB Cycle
Remote mode:
pA/pB SC2
Active line, current operating mode
------------------------------
▶1 pA/pB Clock
·········
pA/pB Cycle
4. Use «Up» or «Down» to set the
pA/pB SC2 input.
5. Press «Enter».
The setting is applied.
Slave IP configuration
The controllers of both machines must be set to different IP addresses.
Example:
■ IP addressController machine 1 (Master mode): 169.254.100.101
■ IP address Controller machine 2 (Slave): 169.254.100.102
Precondition The electrical connection is made.
Access level 2 is activated.
1. Set IP address for the slave: For instructions, see chapter 8.2.14, IP address for the above ex‐
ample.
The IP address of machine 2 (slave) is set correctly.
8
Initial Start-up
8.11 Setting the machine for master control operation
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X