■ Method A: Start the machine via a remote-controlled input signal.
■ Method B: Start the machine via remote control in addition to a preset ON/OFF time pro‐
gramme.
The machine can then be started by remote control, even when time control has been activa‐
ted and the ON/OFF time programme currently specifies OFF.
8.5.4.1 Blower on
Precondition An electrical connection has been established via a free digital input
Access level 2 is activated
The operating mode is displayed
1. Open the menu 5.5
<Configuration – External DI / AII signal>.
The
Blower on function can be used to influence the "Remote On” signal via a digital input DI
1.XX. This signal allows start-up to be enabled via remote operation. In the absence of the
"Remote On" signal, the blower will be prevented from starting remotely, regardless of the op‐
erating mode selected. When the
Blower on function is deactivated, the “Remote On” signal
remains on permanently.
2. Using the «Up» or «Down» key, select the line
Blower on.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.5 External DI / AII signal
Menu
▶1 Current signal AII1.02
Blower on
Active line
DI1.05
☐ Logic :
+
······························
Load signal
DI1.09
☐ Logic :
+
3. Press the «Down» key.
The input
DI has been selected.
4. Press the «Enter» key.
The display flashes for the input currently set.
5. Using the «Up» or «Down» key, select the free input DI.
6. Press the «Enter» key.
The setting is applied accordingly.
7. Press the «Right» key.
8. Press the «Enter» key.
The check box assigned to the input flashes.
9. Press the «Up» key.
The check box is activated.
8
Initial Start-up
8.5
Machine start and machine stop
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
89