8.8.1.1 DO-functions menu
The requested message can be assigned to a free digital output (DOR orDOT).
Precondition Access level 2 is activated.
1. Open the 5.10.1
<Configuration – I/O periphery – DO-functions> menu.
A menu containing a list of available messages and their assigned outputs is displayed.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.10.1 DO-functions
Menu
On load
Active line
DOR1.05
☐ ¦ Logic :
+
······························
Controller on
DOR1.03
☐ ¦ Logic :
+
······························
8.8.1.2 Assigning a message to an output
1. Select the required message with the «Up» or «Down» keys.
2. Press the «Down» key once.
Output DOR has been selected
3. Press «Enter».
The output of the selected message flashes.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.10.1 DO-functions
Menu
On load
DOR1.05
ok
☐ ¦ Logic :
+
Active line with assigned output
······························
Controller on
DOR1.03
☐ ¦ Logic :
+
······························
4. Select a free output with the «Up» or «Down» key.
5. Press «Enter».
The setting is applied.
6. Press the «Right» key.
7. Press «Enter».
The check box will flash.
8. Press «Up» key.
The check box associated to the output is activated.
9. Press «Enter».
If the message is correctly assigned to the output and activated,
ok is displayed.
10. If necessary, set the
Logic option.
Result A message about the operational state is now sent via the assigned digital output.
8
Initial Start-up
8.8
Setting input and output signals
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
123