3. Press the «Enter» key.
Setting mode is active.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
4.1 External counter
External counter 1
Motor running
Active line
3000h¦
2319h
Reset
☐
······························
External counter 2
inactive
4. Use the «Up» or «Down» key to set the desired mode. Possible settings:
■ inactive
■ Motor running
■ On load
5. Press the «Enter» key.
The setting is applied accordingly.
Set maintenance interval
1. Using the «Up» or «Down» key, select the line
External counter 1, for example.
2. Press the «Down» key twice.
3. Press the «Enter» key.
The setting mode is active.
4 0 0 m b a r
0 8 : 1 5 A M
8 0 ° C
Header
4.1 External counter
External counter 1
Motor running
3000h¦
2319h
Reset
☐
Active line
······························
External counter 2
inactive
4. Use the «Up» or «Down» keys to set the new value for the maintenance interval.
Keep the «Up» or «Down» key pressed to change the maintenance interval in increments of
10, 100 or 1000.
5. Press the «Enter» key.
The setting is applied accordingly.
Result The maintenance interval is set.
9
Operation
9.8
External Maintenance counter
148
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
No.: 901700 14 E