The RFID read/write device transmits at a frequency of 13.56 MHz and is permitted for use in
EU member states.
3.1.2 Input/output module
The input/output module features:
■ Internal temperature monitoring
■ Internal undervoltage monitoring
■ LED indication of operational status
IOM 1
Input/Output
Input/output module 1
Internal, in
the control
cabinet
available in
parallel on
both sides
External, into
the machine
interior
Digital input (DI), 24 VDC
4
10
2
Analogue input current (AII), 0–20 mA
–
1
2
Analogue input resistor (AIR), PT100
–
1
3
Digital output relay (DOR), 250 VAC, 8 A
8
–
–
Digital output transistor (DOT), 24 VDC, 0.5 A
–
2
1
Analogue output current (AOI), 0–20 mA
–
–
–
Tab. 12 IOM 1
3.1.2.1 Power supply specifications
Power is provided by the power supply unit within the machine.
Characteristic
Value
Rated voltage (stabilised) [V DC]
24
Current consump‐
tion SIGMA CONTROL 2 with IOM 1 [A]
2.4
IOM ≙ Input/Output module
Tab. 13 Power supply specifications
3.1.2.2 Maximum cable lengths
Input/Output
Cable length [m]
Analogue input current (AII),
Analogue input resistor (AIR)
Analogue output current (AOI)
< 30
Digital input (DI),
Digital output relay (DOR)
< 100
Digital output transistor (DOT)
< 30
Tab. 14 Cable lengths
3
Technical Specifications
3.1
Controller SIGMA CONTROL 2
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X
11