6. Set the e-mail parameters as described above:
If SIGMA CONTROL 2 is connected via SIGMA NETWORK to SAM 4.0 and emails are to be
forwarded via SAM 4.0, then enter the IP address of interface X6 of SAM 4.0 in the
SMTP
server: field. 169.254.100.100 (see also chapter 8.7.2). Enter at port address of the SMTP
server: 25.
For SAM 4.0 the option
Data Forwarding in the menu <Configuration - E-mail - Basic Set‐
tings> must be activated.
Parameter
Setting
value
Meaning
Blower
number:
This field displays the machine number that appears as the sender of e-
mails. The recipient is thus able to identify the different machines send‐
ing mails.
Language:
Use this field to define the language for the message texts. This setting
is independent from the language setting in SIGMA CONTROL 2 (see
Repeat cut-off
time:
In this field, enter the time in minutes (repeat block time) that the system
must wait in order not to send multiple recurring messages in short time
intervals.
Use SSL:
E-mail sending is encrypted if the check box is ticked.
Sender
address:
Enter the e-mail address of the sender in this field.
Sender name:
Enter the name of the sender in this field.
Contact
telephone:
In this field, enter a telephone number under which the air station opera‐
tor can be reached. This telephone number is sent with each e-mail.
Receiver
address:
The e-mail address of the recipient
SMTP server:
IP address of the SMTP server receiving and forwarding the e-mails
User name:
Log-in user name for logging on to the SMTP server
Password:
Log-in password for logging on to the SMTP server
Port
Port address of the SMTP server
Timeout
In this field, enter the seconds for SIGMA CONTROL 2 to wait for a reply
by the SMTP server before e-mail sending is cancelled.
Resend after:
In this field, enter the time in seconds for the system to wait after a failed
e-mail sending operation before it again attempts to send the mail.
Tab. 58 E-mail parameters
7. Activating the e-mail function: Activate the
active: check box as described above.
8. Press «Escape» repeatedly to leave this menu.
Result The e-mail parameters are set and the e-mail function is activated.
Suppressing repeat messages
To suppress messages repeating at short intervals, a period of 0–999 minutes can be set during
which a repeat of the same message is suppressed, i.e. is not sent. This prevents the sending of
identical messages.
8
Initial Start-up
8.2
Setting the controller
No.: 901700 14 E
Service Manual Controller
SIGMA CONTROL 2 BLOWER ≥ 4.0.X